Plan Review Notes For Permit 20090465 |
Permit Number |
20090465 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-03-25 16:22:51 | 2ND REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20090465 | | 3/25/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | PREVIOUS REVIEW COMMENT NOT ADDRESSED. | | AFTER REVIEWING THE COMMENT BELOW PLEASE CONTACT ME . | | | | 1) PLEASE SHOW THE PE LINE TO THE NEW GENERATOR THAT IS | | CURRENTLY BEING INSPECTED UNDER PERMIT 20041075. SHOW | | THE PE PIPING POINT OF CONNECTION TO THE SCHEDULE 40 | | AND ADD THE 575,000 BTU LOAD OF THE GENERATOR TO THE | | TOTAL LOAD OF THE SYSTEM- SECTIONS G2413.3 & G2413.4 | | FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|