Plan Review Notes For Permit 20090465 |
Permit Number |
20090465 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-03-22 13:52:08 | 2ND REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20090465 | | 3/22/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SHOW THE PE LINE TO THE NEW GENERATOR THAT IS | | CURRENTLY BEING INSPECTED UNDER PERMITS 20041074 & | | 20041075. SHOW THE PE PIPING POINT OF CONNECTION TO THE | | SCHEDULE 40 AND ADD THE 575,000 BTU LOAD OF THE | | GENERATOR TO THE TOTAL LOAD OF THE SYSTEM- SECTIONS | | G2413.3 & G2413.4 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|