Plan Review Notes
Plan Review Notes For Permit 20090465
Permit Number 20090465
Review Stop G
Sequence Number 2
Notes
Date Text
2021-03-22 13:52:082ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090465
 3/22/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE PE LINE TO THE NEW GENERATOR THAT IS
 CURRENTLY BEING INSPECTED UNDER PERMITS 20041074 &
 20041075. SHOW THE PE PIPING POINT OF CONNECTION TO THE
 SCHEDULE 40 AND ADD THE 575,000 BTU LOAD OF THE
 GENERATOR TO THE TOTAL LOAD OF THE SYSTEM- SECTIONS
 G2413.3 & G2413.4 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  