Plan Review Notes
Plan Review Notes For Permit 20090442
Permit Number 20090442
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-05 16:18:252ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20090442
 2/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 WATER ISOMETRIC AND WATER PLAN:
  
 A) INSTA-HOT WATER HEATERS LABELED ON PLAN NOT SHOWN ON
 THE ISOMETRIC- SECTION 107.2.1 WPB.
  
 B) LOCATION OF WATER HEATER EXPANSION TANK SHOWN ON HOT
 WATER PIPE IS NOT IN COMPLIANCE WITH SECTION 607.3 FBC
 P. CORRECT LOCATION ON THE COLD WATER INLET PIPE IS
 SHOWN IN THE WATER HEATER DETAIL.
  
 C) TWO BATCH BREWERS ARE SHOWN BUT THE ISOMETRIC AND
 PLAN SHOW ONLY ONE FILTERED WATER LINE CONNECTION-
 SECTION 107.2.1 WPB.
  
 D) WATER SUPPLY CONNECTION TO ESPRESSO MACHINE AND
 RINSER SHOWN ON THE ISOMETRIC BUT ON THE PLAN- SECTION
 107.2.1 WPB.
  
 E) PROVIDE A BACKFLOW DEVICE FOR THE WATER SUPPLY TO
 THE RINSER AND INDICATE THE MAKE AND MODEL OF ALL
 BACKFLOW DEVICES SHOWN ON THE RISER- SECTION 608.3 FBC
 P.
  
 F) PROVIDE WATER HAMMER ARRESTORS FOR SUPPLY LINES TO
 THE FILTRATION SYSTEM, BATCH BREWERS, EXPRESSO MACHINE
 ETC.- SECTION 604.9 FBC P.
  
 G) THERE IS A NOTE INDICATING WATER SUPPLY TO THE
 KETTLES HOWEVER THE WATER SUPPLY LINES ARE NOT SHOWN-
 SECTION 107.2.1 WPB.
  
 H) INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO THE
 LAVATORY- SEE SECTIONS 416.5 AND 607.1.2 FBC P.
  
 I) IT APPEARS A 3/4 IN. HOT WATER PIPE IS SUPPLYING THE
 NEW LAVATORY. PLEASE SEE SECTION C404.5.1 AND TABLE
 C404.5.1 FBC EC- A 3/4 IN. PIPE IS LIMITED TO A MAXIMUM
 LENGTH OF 0.5 FT. FROM THE NEAREST HOT WATER SOURCE.
  
 2) SHEET P1.0: THE SANITARY ISOMETRIC APPEARS TO SHOW A
 SINGLE DRAIN PIPE FROM THE 3-COMPARTMENT SINK
 DISCHARGING INTO THE FLOOR SINK. PLEASE SEE SECTION
 802.1.1 FBC P AND PROVIDE A DETAIL SHOWING EACH WELL OF
 THE SINK DISCHARGING INDEPENDENTLY INTO THE FLOOR SINK.
 3) P1.0: PLEASE ADD SLAB CUTTING FOR UNDERGROUND DRAINS
 AND WATER SUPPLY PIPING IN THE PLUMBING DEMOLITION
 NOTES- SECTION 107.2.1 WPB. REFERENCE IS MADE TO A SLAB
 REPAIR DETAIL ON SHEET A4.0 HOWEVER THERE IS NO SHEET
 A4.0 IN THE SET- SECTION 107.2.1 WPB.
  
 4) P1.0 PLUMBING SPECIFICATIONS: PROVIDE DWV AND WATER
 SUPPLY AND FILTERED WATER SUPPLY PIPING MATERIAL
 SPECIFICATIONS, AND THE TYPE AND SIZE OF HOT WATER PIPE
 INSULATION- SECTIONS303.1 & 303.2 FBC P, AND TABLE
 C403.2.10 FBC EC.
  
 5) P1.0: INDICATE HOW UNDER SLAB WATER PIPING WILL
 PROTECTED FROM CORROSION- SECTION 305.1 FBC P.
  
 6) P1.0- MISSING ACCESSIBILITY DETAILS- FBC- ACC.
 A) WATER CLOSET AND LAVATORY CLEAR FLOOR SPACE
 DIMENSIONS- SECTIONS 604.3 & 606.2.
 B) GRAB LOCATIONS AND LENGTHS NOT SHOWN CORRECTLY
 ACCORDING TO SECTION 604.5 & FIGURES 604.5.1 & 604.5.2
 C) LAVATORY KNEE AND TOE CLEARANCES- SECTION 606.2.
  
 7) 2ND REQUEST FOR PLUMBING FIXTURES CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  