2020-09-24 17:15:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090442 2600 FLORIDA AVE
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 ADDED COMMENT: PER WPB FBC 107.2.1, PROVIDE BUILDING
 KEY PLAN AND INDICATE THE TENANT SPACE FOOTPRINT IN THE
 BUILDING
 ADDED COMMENT: PER WPB FBC 107.2.1, PROVIDE
 CALCULATIONS FOR SIZING OF GREASE INTERCEPTOR
  
 1.A REVIEW OF PUBLIC RECORDS PRESENT AN UNCLEAR
 UNDERSTANDING OF THE EXISTING SPACE. BY ALL ACCOUNTS
 THE LAST CHANGE OF OCCUPANCY WAS FROM AUTO REPAIR TO
 ART STUDIO (SEE PAST PERMITS 14100679 EXPIRED AND
 SUBSEQUENT PERMIT 15020882 DATED 2/26/2015 FOR
 INSPECTION DUE TO FAILED COP) THERE ARE NO PERMIT PLANS
 ON RECORD FOR THAT CHANGE OF OCCUPANCY. AS SUCH, THE
 PERMIT NEEDS TO ADDRESS THE EXISTING CONDITIONS AS WELL
 AS THE REQUESTED CHANGES AND SHALL COMPLY WITH 2017
 FLORIDA BUILDING CODE, 2017 FLORIDA ACCESSIBILITY CODE
 AND 2017 FLORIDA PLUMBING CODE PER WPB FBC SECTION
 107.3.5.1.3 PLUMBING .
 2.PER WPB FBC 107.2.1, PROVIDE PLAN AND ELEVATION
 DETAILS OF BATHROOM SHOWING COMPLIANCE WITH THE
 PROVISION OF FBC ACC CHAPTERS 3 AND 6.
 3.PER WPB FBC 107.2.1, PROVIDE WALL SCHEDULE/DETAILS
 FOR BATHROOM SHOWING COMPLIANCE WITH FBC 1210.2.1 AND
 1210.2.2.
 4.P-1 PLAN VIEW SHOWS HOT AND COLD WATER TO NEW SINKS
 CONNECTED TO ADJACENT TENANT SPACE. CONNECT WITHIN THE
 TENANT SPACE BEING PERMITTED. PER WPB FBC 107.2.1,
 PROVIDE SIZED HOT AND COLD WATER RISER DIAGRAM OF
 COMPLETE SYSTEM (INCLUDING FILTERED). SHOW ALL VALVES,
 REQUIRED BACKFLOW DEVICES, EQUIPMENT AND APPURTENANCES
 (WATER HEATER, FILTERS, COFFEE BREWER, ETC.). FLOOR
 PLAN AND RISER DIAGRAM SHALL BE IN AGREEMENT.
 5.PROVIDE SCHEDULE AND DETAIL OF WATER HEATER SHOWING
 HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, HW,
 VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC
 PL 504.2) , THERMAL EXPANSION CONTROL DEVICE (INCLUDING
 SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER
 HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER WPB
 FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, 504.1,
 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2.
 6.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR WATER FILTRATION
 SYSTEM.
 7.PER FBC PL 1003.1, PROVIDE A GREASE INTERCEPTOR FOR
 THE THREE-COMPARTMENT SINK. PER WPB FBC 107.2.1,
 PROVIDE SPECIFICATION FOR INTERCEPTOR AND DETAIL OF
 SINK AND INTERCEPTOR, SHOWING HOW DISCHARGED TO
 SANITARY FLOOR SINK.
 8.PER WPB FBC 107.2.1, INDICATE ON PLAN ALL ITEMS (I.E.
 EXPRESSO MACHINE, FILTRATION SYSTEM) THAT ARE TO
 DISCHARGE TO SANITARY AND HOW THEY WILL DISCHARGE (I.E.
 TO HUB DRAIN THROUGH (SIZED) INDIRECT WASTE WITH AIR
 GAP)
 9.SANITARY RISER DIAGRAM AND FLOOR PLAN SHALL BE
 COMPLETE AND SHALL BE IN AGREEMENT.
 10.CLEANOUT REQUIRED AT JUNCTION OF SANITARY BUILDING
 DRAIN AND BUILDING SEWER PER FBC PL 708.1.3.
 11.PER FBC PL 904.1, THE VENT SYSTEM SERVING EACH
 BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE VENT PIPE
 THAT EXTENDS TO THE OUTDOORS.
 12.1002.4.1TRAP SEAL PROTECTION.PER FBC PL 1002.4.1,
 TRAP SEALS OF FLOOR DRAIN TRAPS AND TRAP SEALS SUBJECT
 TO EVAPORATION SHALL BE PROTECTED BY ONE OF THE METHODS
 IN SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  