Date |
Text |
2020-09-24 17:15:20 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 20090442 2600 FLORIDA AVE |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| ADDED COMMENT: PER WPB FBC 107.2.1, PROVIDE BUILDING |
| KEY PLAN AND INDICATE THE TENANT SPACE FOOTPRINT IN THE |
| BUILDING |
| ADDED COMMENT: PER WPB FBC 107.2.1, PROVIDE |
| CALCULATIONS FOR SIZING OF GREASE INTERCEPTOR |
| |
| 1.A REVIEW OF PUBLIC RECORDS PRESENT AN UNCLEAR |
| UNDERSTANDING OF THE EXISTING SPACE. BY ALL ACCOUNTS |
| THE LAST CHANGE OF OCCUPANCY WAS FROM AUTO REPAIR TO |
| ART STUDIO (SEE PAST PERMITS 14100679 EXPIRED AND |
| SUBSEQUENT PERMIT 15020882 DATED 2/26/2015 FOR |
| INSPECTION DUE TO FAILED COP) THERE ARE NO PERMIT PLANS |
| ON RECORD FOR THAT CHANGE OF OCCUPANCY. AS SUCH, THE |
| PERMIT NEEDS TO ADDRESS THE EXISTING CONDITIONS AS WELL |
| AS THE REQUESTED CHANGES AND SHALL COMPLY WITH 2017 |
| FLORIDA BUILDING CODE, 2017 FLORIDA ACCESSIBILITY CODE |
| AND 2017 FLORIDA PLUMBING CODE PER WPB FBC SECTION |
| 107.3.5.1.3 PLUMBING . |
| 2.PER WPB FBC 107.2.1, PROVIDE PLAN AND ELEVATION |
| DETAILS OF BATHROOM SHOWING COMPLIANCE WITH THE |
| PROVISION OF FBC ACC CHAPTERS 3 AND 6. |
| 3.PER WPB FBC 107.2.1, PROVIDE WALL SCHEDULE/DETAILS |
| FOR BATHROOM SHOWING COMPLIANCE WITH FBC 1210.2.1 AND |
| 1210.2.2. |
| 4.P-1 PLAN VIEW SHOWS HOT AND COLD WATER TO NEW SINKS |
| CONNECTED TO ADJACENT TENANT SPACE. CONNECT WITHIN THE |
| TENANT SPACE BEING PERMITTED. PER WPB FBC 107.2.1, |
| PROVIDE SIZED HOT AND COLD WATER RISER DIAGRAM OF |
| COMPLETE SYSTEM (INCLUDING FILTERED). SHOW ALL VALVES, |
| REQUIRED BACKFLOW DEVICES, EQUIPMENT AND APPURTENANCES |
| (WATER HEATER, FILTERS, COFFEE BREWER, ETC.). FLOOR |
| PLAN AND RISER DIAGRAM SHALL BE IN AGREEMENT. |
| 5.PROVIDE SCHEDULE AND DETAIL OF WATER HEATER SHOWING |
| HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, HW, |
| VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC |
| PL 504.2) , THERMAL EXPANSION CONTROL DEVICE (INCLUDING |
| SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER |
| HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER WPB |
| FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, 504.1, |
| 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND |
| 504.7.2. |
| 6.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| SPECIFICATION/INSTALLATION MANUAL FOR WATER FILTRATION |
| SYSTEM. |
| 7.PER FBC PL 1003.1, PROVIDE A GREASE INTERCEPTOR FOR |
| THE THREE-COMPARTMENT SINK. PER WPB FBC 107.2.1, |
| PROVIDE SPECIFICATION FOR INTERCEPTOR AND DETAIL OF |
| SINK AND INTERCEPTOR, SHOWING HOW DISCHARGED TO |
| SANITARY FLOOR SINK. |
| 8.PER WPB FBC 107.2.1, INDICATE ON PLAN ALL ITEMS (I.E. |
| EXPRESSO MACHINE, FILTRATION SYSTEM) THAT ARE TO |
| DISCHARGE TO SANITARY AND HOW THEY WILL DISCHARGE (I.E. |
| TO HUB DRAIN THROUGH (SIZED) INDIRECT WASTE WITH AIR |
| GAP) |
| 9.SANITARY RISER DIAGRAM AND FLOOR PLAN SHALL BE |
| COMPLETE AND SHALL BE IN AGREEMENT. |
| 10.CLEANOUT REQUIRED AT JUNCTION OF SANITARY BUILDING |
| DRAIN AND BUILDING SEWER PER FBC PL 708.1.3. |
| 11.PER FBC PL 904.1, THE VENT SYSTEM SERVING EACH |
| BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE VENT PIPE |
| THAT EXTENDS TO THE OUTDOORS. |
| 12.1002.4.1TRAP SEAL PROTECTION.PER FBC PL 1002.4.1, |
| TRAP SEALS OF FLOOR DRAIN TRAPS AND TRAP SEALS SUBJECT |
| TO EVAPORATION SHALL BE PROTECTED BY ONE OF THE METHODS |
| IN SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4. |
| |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE FIRST REVIEW. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20090442 2600 FLORIDA AVE |