2020-10-03 10:55:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER DIAGRAM DOES NOT SHOW SIZE OF CONDUCTORS.
 PLEASE INDICATE THE SIZE OF THE FEEDER CONDUCTORS.
  
 2) FAULT CURRENT CALCULATION REQUIRED FOR SERVICE AND
 NEW PANEL 110.9, 110.10. PROVIDE LABEL AT SERVICE FOR
 AIC RATING PER 110.24
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 3) PLEASE INDICATE LIGHTING LAYOUT AND LIGHTING
 CONTROL, SHOW NUMBER OF USB OUTLETS UNDER THE COUNTER.
  
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  
 4) LOAD CALCULATION DOES NOT INCLUDE RECEPTACLE
 OUTLETS, SIGN CIRCUIT, DISPLAY LIGHTING, USB OUTLETS,
 ECT. ECT.