Plan Review Notes For Permit 20090435 |
Permit Number |
20090435 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-24 13:12:17 | SIDING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) EXTERIOR WALL SIDING IS SUBJECT TO WIND LOADS PER | | FBC R301.1 PLEASE PROVIDE THE STRUCTURAL CALCULATIONS | | REQUIRED FOR THESE LOADS OR HAVE THE DETAILS PREPARED | | AND SIGNED AND SEALED BY AN ARCHITECT OR ENGINEER FBC | | R301.1.3 - OR- PROVIDE A MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVAL FOR THE SIDING (COMPLETE PRODUCT | | APPROVAL - FRONT PAGES AND THE INSTALLATION | | INSTRUCTIONS) | | 2) PLEASE SHOW THE WIND DESIGN DATA PER FBC R301.2.1 | | 3) DRAWINGS NEED TO SHOW ALL ATTACHMENTS (SIZE, TYPE | | AND SPACING). | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG | | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON | | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW | | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] | | AND ASKING FOR THE FORM. | | |
|