Plan Review Notes For Permit 20090357 |
Permit Number |
20090357 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-16 11:31:23 | 1ST REVIEW FBC-2017 PLUMBING | | PERMIT-20090357 | | 9/16/2020 | | | | CODES IN EFFECT: | | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | TO THE FBC SEC. 105.1. | | | | 2. A SUB IRRIGATION PERMIT IS REQUIRED BY A LICENSED | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | TO THE FBC SEC. 105.1. | | | | 3. THE PLUMBING PLAN SHALL BEAR THE TITLE BLOCK AND | | ELECTRONIC SEAL AND SIGNATURE OF THE FL. LICENSED | | ARCHITECT OR ENGINEER WHO PREPARED THE DRAWING- SECTION | | 107.2.1 WPB, FL. STATUTES 471.025 & 481.221, AND | | SECTIONS 61G15-23.005 & 61G1-16.005 FAC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | ATELYO BELISLE | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6695 | | |
|