 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, FBC M 401 & GENERAC SPECIFICATIONS (SITE
 SELECTIONS), THE LOCATION OF EXHAUST TERMINATION SHOULD
 BE INDICATED ON PLAN, MUST BE AT NO LESS THAN 10'
 HORIZONTALLY OR 3' VERTICALLY ABOVE THE OPERABLE
 OPENINGS OF THE STRUCTURE.