Plan Review Notes
Plan Review Notes For Permit 20090345
Permit Number 20090345
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-18 17:15:081ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090435
 9/18/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
 A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM,
 AND THE LENGTHS OF THE BRANCHES TO THE INTERIOR AND THE
 POOL HEATER- SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 B) INDICATE THE TOTAL LOAD OF THE SYSTEM- 1,126,000
 BTUH PER SECTION G2413.2
 C) PIPE SIZING TABLE 402.4(3) SHOWN ON THE RISER HAS AN
 INITIAL SUPPLY PRESSURE OF 8.0 IN. WC. AND A PRESSURE
 DROP OF 3.0 IN. WC. THIS APPEARS TO BE THE INCORRECT
 SIZING TABLE BECAUSE COMMON RESIDENTIAL LOW PRESSURE
 PIPING SYSTEMS ARE DESIGNED AT A PRESSURE AROUND 7 IN.
 WC. AND A PRESSURE DROP OF 0.5 IN. WC. THE PIPING MUST
 BE SIZED SUFFICIENTLY ENOUGH SO THAT THE PRESSURE DROP
 IS A HALF AN INCH OF WATER COLUMN OR LESS, WHEN ALL THE
 GAS APPLIANCES ARE ON. THE CALCULATED DROPPED PRESSURE
 (THE STATIC PRESSURE MINUS THE 3.0 IN. PRESSURE DROP),
 MUST BE GREATER THAN THE HIGHEST MINIMUM GAS PRESSURE
 REQUIRED BY ANY OF THE GAS APPLIANCES ON THE SYSTEM.
 PLEASE REFER TO TABLES G2413.4(1)- G2413.4(8) FBC RES.
 TABLE G2413.4(1) IS THE TYPICAL LOW PRESSURE SIZING
 TABLE USED. THE RELATIVE TABLE IN THE FBC FG IS
 {402.4(2). USING THIS TABLE THE 1 IN. SCHEDULE 40
 METALLIC PIPES SHOWN DOWNSTREAM OF THE REGULATOR AND
 METER, AT A MINIMUM SHALL BE SIZED AT 1-1/2 INCHES FOR
 THE TOTAL 1,126,000 BTUH LOAD. PLEASE NOTE THE 1-1/2
 IN. PIPE WILL MAX OUT FOR THE SYSTEM AT A TOTAL
 DEVELOPED LENGTH OF 30 FT. A SECOND OPTION WOULD BE TO
 INSTALL A 2.0 PSI REGULATOR AT THE METER IF POSSIBLE
 AND LOW PRESSURE REGULATORS FOR THE BRANCHES AND
 APPLIANCES.
 D) PROVIDE THE MAKE AND MODEL OF THE SELECTED REGULATOR
 ON THE RISER, AND MARK UP OR HIGHLIGHT THE SPEC SHEETS
 TO SHOW THE MODEL, INLET AND OUTLET PRESSURES, SPRING
 SELECTION, AND ORIFICE SIZE- SECTION G2421.1 & G2421.2.
 E) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
  
 2) SURVEY: CORRECT THE 5 FT. CLEARANCE TO WINDOW AND
 DOOR OPENINGS PER SECTION R303.5.1 FBC RES. A MINIMUM
 10 FT. CLEARANCE IS REQUIRED. VERIFY THE ADJACENT HOUSE
 WALL IS NON-COMBUSTIBLE AND HAS A 1-HR. FIRE-RESISTANCE
 RATING, OTHERWISE A 5 FT. CLEARANCE IS REQUIRED PER
 SEC. 4.1.4 NFPA 37. PROVIDE THE CLEARANCE DISTANCE TO
 THE ADJACENT PROPERTY LINE- IT IS INDICATED AS 8.5 FT.
 FROM THE STRUCTURE- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  