2020-09-30 11:29:51 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20090342 |
| 9/30/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: PIPE SIZING FOR A SCHED. 40 |
| METALLIC 2-PSI SYSTEM SHALL BE IN ACCORDANCE WITH TABLE |
| G2413.4(2) FBC RES. OR THE EQUIVALENT TABLE 402.4(5) |
| FBC FG. A LOW PRESSURE PIPE SIZING TABLE 402.4(3) IS |
| SHOWN ON THE DRAWING, HOWEVER YOU SHOW A 2-PSI |
| REGULATOR AT THE METER. IS THIS A LOW PRESSURE SYSTEM |
| OR A 2-PSI SYSTEM? WHAT IS THE REGULATOR OUTLET |
| DELIVERY PRESSURE? |
| |
| A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN |
| AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM- |
| SECTIONS G2413.4.1 AND G2413.4.2 FBC RES. |
| |
| B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE |
| CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL |
| AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR |
| NATURAL GAS. PLEASE CORRECT THE INDIVIDUAL AND TOTAL |
| LOADS ON THE RISER- SECTION G2413.2 FBC RES. & 107.2.1 |
| WPB. |
| |
| C) SHOW THE INLET AND OUTLET PRESSURES AT THE B31 |
| REGULATOR- SECTION G2421.1 & G2421.2. PLEASE NOTE THAT |
| THE MARKED UP OR HIGHLIGHTED SPECS SHALL BE ONSITE FOR |
| INSPECTION. THE SPECS SHALL INDICATE THE REGULATOR IS |
| RATED FOR OUTDOOR USE, AND BE MARKED TO SHOW THE |
| SELECTED MODEL, PRESSURES, SPRING SELECTION, AND |
| ORIFICE SIZE. |
| |
| 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM |
| OF 5' AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, |
| AND A MINIMUM OF 10' FROM MECHANICAL OR GRAVITY AIR |
| INTAKES (WINDOW AND DOOR OPENINGS) INTO THE BUILDING- |
| SEC. R303.5.1 FBC RES. PLEASE CORRECT THE NOTES ON THE |
| DRAWING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |