2020-09-30 11:29:511ST REVIEW FBC-2017 RES.
 PERMIT- 20090342
 9/30/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PIPE SIZING FOR A SCHED. 40
 METALLIC 2-PSI SYSTEM SHALL BE IN ACCORDANCE WITH TABLE
 G2413.4(2) FBC RES. OR THE EQUIVALENT TABLE 402.4(5)
 FBC FG. A LOW PRESSURE PIPE SIZING TABLE 402.4(3) IS
 SHOWN ON THE DRAWING, HOWEVER YOU SHOW A 2-PSI
 REGULATOR AT THE METER. IS THIS A LOW PRESSURE SYSTEM
 OR A 2-PSI SYSTEM? WHAT IS THE REGULATOR OUTLET
 DELIVERY PRESSURE?
  
 A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE INDIVIDUAL AND TOTAL
 LOADS ON THE RISER- SECTION G2413.2 FBC RES. & 107.2.1
 WPB.
  
 C) SHOW THE INLET AND OUTLET PRESSURES AT THE B31
 REGULATOR- SECTION G2421.1 & G2421.2. PLEASE NOTE THAT
 THE MARKED UP OR HIGHLIGHTED SPECS SHALL BE ONSITE FOR
 INSPECTION. THE SPECS SHALL INDICATE THE REGULATOR IS
 RATED FOR OUTDOOR USE, AND BE MARKED TO SHOW THE
 SELECTED MODEL, PRESSURES, SPRING SELECTION, AND
 ORIFICE SIZE.
  
 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM
 OF 5' AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37,
 AND A MINIMUM OF 10' FROM MECHANICAL OR GRAVITY AIR
 INTAKES (WINDOW AND DOOR OPENINGS) INTO THE BUILDING-
 SEC. R303.5.1 FBC RES. PLEASE CORRECT THE NOTES ON THE
 DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  