2020-09-25 16:34:28 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20090339 |
| 9/25/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 9018 LAKES |
| BLVD. SHOW GAS PERMIT #99071571 ISSUED 9/17/1999 FOR |
| INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS |
| INDICATE A TOTAL LOAD OF 448,000 BTU'S: POOL HEATER- |
| 325,000. GRILL- 35,000. COOKTOP- 30,000. DRYER- 22,000. |
| WATER HEATER- 36,000. REVISE THE RISER TO SHOW THE |
| COMPLETE PIPING SYSTEM INCLUDING PIPE RUNS TO ALL NEW |
| AND EXISTING APPLIANCES AND EQUIPMENT, AND SHOW THE |
| CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM- |
| SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE |
| NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS |
| INDICATED TO BE 60FT., AND THE POOL HEATER AND GRILL |
| WERE LISTED AS OPTIONAL ON THE APPROVED PLAN. PLEASE |
| VERIFY IN FIELD THAT THE APPLIANCES ARE INSTALLED |
| BEFORE RESUBMITTING PLANS. |
| |
| A) REVISE THE DRAWING TO SHOW THE TOTAL LENGTH OF THE |
| INTERIOR PIPING RUN AND THE TOTAL DEVELOPED LENGTH OF |
| THE ENTIRE SYSTEM- SECTIONS G2413.4.1 AND G2413.4.2 FBC |
| RES. |
| |
| B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE |
| CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL |
| AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR |
| NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER |
| TO INDICATE 870,000 BTUH. |
| |
| C) PIPE SIZING SHALL BE IN ACCORDANCE WITH SECTION |
| G2413.3 FBC RES. TABLE 402.4(3) FBC FG WITH A 3.0 IN. |
| PRESSURE DROP LISTED ON THE PLANS IS NOT A SIZING TABLE |
| FOUND IN THE FBC RES. TYPICALLY PRESSURE DROP IN |
| RESIDENTIAL LOW PRESSURE SYSTEMS IS 0.5 IN. W.C. PLEASE |
| REVIEW SECTION G2413.5 (402.5 ) ALLOWABLE PRESSURE DROP |
| WHICH INDICATES: |
| THE DESIGN PRESSURE LOSS IN ANY PIPING SYSTEM UNDER |
| MAXIMUM PROBABLE FLOW CONDITIONS, FROM THE POINT OF |
| DELIVERY TO THE INLET CONNECTION OF THE APPLIANCE, |
| SHALL BE SUCH THAT THE SUPPLY PRESSURE AT THE APPLIANCE |
| IS GREATER THAN OR EQUAL TO THE MINIMUM PRESSURE |
| REQUIRED BY THE APPLIANCE. |
| |
| D) PLEASE INDICATE THE SIZING METHOD USED PER SECTIONS |
| G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH LENGTH. |
| INDICATE THE TABLES USED TO SIZE THE SCHEDULE 40 |
| METALLIC- SEE TABLES G2413.4(1)- G2413.4(8). PLEASE |
| NOTE IF USING THE LONGEST LENGTH METHOD TO SIZE THE |
| SCHED. 40 METALLIC, THE MAIN PIPE FROM THE METER TO THE |
| 1ST TEE, ACCORDING TO TABLE G2413.4(1) [402.4(2)] SHALL |
| BE MINIMUM 1-1/2 IN. FOR A 754,000 BTUH LOAD AT 60 FT. |
| DEVELOPED LENGTH. |
| |
| 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM |
| OF 5FT. AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA |
| 37, AND A MINIMUM OF 10 FT. FROM MECHANICAL OR GRAVITY |
| AIR INTAKES (WINDOW AND DOOR OPENINGS) INTO THE |
| BUILDING- SEC. R303.5.1 FBC RES. CORRECT THE NOTES ON |
| THE DRAWING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |