Plan Review Notes
Plan Review Notes For Permit 20090339
Permit Number 20090339
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-25 16:34:281ST REVIEW FBC-2017 RES.
 PERMIT- 20090339
 9/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 9018 LAKES
 BLVD. SHOW GAS PERMIT #99071571 ISSUED 9/17/1999 FOR
 INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS
 INDICATE A TOTAL LOAD OF 448,000 BTU'S: POOL HEATER-
 325,000. GRILL- 35,000. COOKTOP- 30,000. DRYER- 22,000.
 WATER HEATER- 36,000. REVISE THE RISER TO SHOW THE
 COMPLETE PIPING SYSTEM INCLUDING PIPE RUNS TO ALL NEW
 AND EXISTING APPLIANCES AND EQUIPMENT, AND SHOW THE
 CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM-
 SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE
 NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS
 INDICATED TO BE 60FT., AND THE POOL HEATER AND GRILL
 WERE LISTED AS OPTIONAL ON THE APPROVED PLAN. PLEASE
 VERIFY IN FIELD THAT THE APPLIANCES ARE INSTALLED
 BEFORE RESUBMITTING PLANS.
  
 A) REVISE THE DRAWING TO SHOW THE TOTAL LENGTH OF THE
 INTERIOR PIPING RUN AND THE TOTAL DEVELOPED LENGTH OF
 THE ENTIRE SYSTEM- SECTIONS G2413.4.1 AND G2413.4.2 FBC
 RES.
  
 B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE
 CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL
 AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR
 NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER
 TO INDICATE 870,000 BTUH.
  
 C) PIPE SIZING SHALL BE IN ACCORDANCE WITH SECTION
 G2413.3 FBC RES. TABLE 402.4(3) FBC FG WITH A 3.0 IN.
 PRESSURE DROP LISTED ON THE PLANS IS NOT A SIZING TABLE
 FOUND IN THE FBC RES. TYPICALLY PRESSURE DROP IN
 RESIDENTIAL LOW PRESSURE SYSTEMS IS 0.5 IN. W.C. PLEASE
 REVIEW SECTION G2413.5 (402.5 ) ALLOWABLE PRESSURE DROP
 WHICH INDICATES:
 THE DESIGN PRESSURE LOSS IN ANY PIPING SYSTEM UNDER
 MAXIMUM PROBABLE FLOW CONDITIONS, FROM THE POINT OF
 DELIVERY TO THE INLET CONNECTION OF THE APPLIANCE,
 SHALL BE SUCH THAT THE SUPPLY PRESSURE AT THE APPLIANCE
 IS GREATER THAN OR EQUAL TO THE MINIMUM PRESSURE
 REQUIRED BY THE APPLIANCE.
  
 D) PLEASE INDICATE THE SIZING METHOD USED PER SECTIONS
 G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH LENGTH.
 INDICATE THE TABLES USED TO SIZE THE SCHEDULE 40
 METALLIC- SEE TABLES G2413.4(1)- G2413.4(8). PLEASE
 NOTE IF USING THE LONGEST LENGTH METHOD TO SIZE THE
 SCHED. 40 METALLIC, THE MAIN PIPE FROM THE METER TO THE
 1ST TEE, ACCORDING TO TABLE G2413.4(1) [402.4(2)] SHALL
 BE MINIMUM 1-1/2 IN. FOR A 754,000 BTUH LOAD AT 60 FT.
 DEVELOPED LENGTH.
  
 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM
 OF 5FT. AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA
 37, AND A MINIMUM OF 10 FT. FROM MECHANICAL OR GRAVITY
 AIR INTAKES (WINDOW AND DOOR OPENINGS) INTO THE
 BUILDING- SEC. R303.5.1 FBC RES. CORRECT THE NOTES ON
 THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  