2020-10-19 18:30:31 | 010/19/20 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THIS IS A RESTAURANT AND IT REQUIRES A CHANGE OF |
| OCCUPANCY. THERE IS NO APPLICATION OR PERMITS FOR THIS |
| SCOPE OF WORK. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY |
| THIS INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. A GREASE TRAP MAY BE REQUIRED ALONG WITH SIZING, A |
| SEPARATE PERMIT AND APPLICATION WILL BE NEED IF SO 2017 |
| FBC P 1003.1. |
| |
| 3. SUBMIT PLANS SHOWING THE LOCATION OF THE TANK-LESS |
| WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 4. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| |
| 5. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS |
| IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER |
| THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017 |
| FBC FG SEC. 304.9.3. COMBINED COMBUSTION AIR AND |
| VENTILATION AIR SYSTEM. |
| |
| 7. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE |
| GAS SYSTEM OR PLACE A NOTE ON SET OF PLANS LISTING THE |
| SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT |
| WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC |
| FG SEC. 402.3. |
| |
| 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| 10.4, 10.5 OF NFPA 96-08. |
| |
| 9. PROVIDE THE SIGNATURE OF ALL INFORMATION OF DATA |
| SHALL BEAR THE PRINTED NAME OF THE SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |