Plan Review Notes
Plan Review Notes For Permit 20090291
Permit Number 20090291
Review Stop G
Sequence Number 2
Notes
Date Text
2020-10-19 18:30:31010/19/20 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS IS A RESTAURANT AND IT REQUIRES A CHANGE OF
 OCCUPANCY. THERE IS NO APPLICATION OR PERMITS FOR THIS
 SCOPE OF WORK. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY
 THIS INTERIOR BUILD-OUT WILL BE AND THE OCCUPANCY LOAD
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. A GREASE TRAP MAY BE REQUIRED ALONG WITH SIZING, A
 SEPARATE PERMIT AND APPLICATION WILL BE NEED IF SO 2017
 FBC P 1003.1.
  
 3. SUBMIT PLANS SHOWING THE LOCATION OF THE TANK-LESS
 WATER HEATER AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 5. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS
 IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 6. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC FG SEC. 304.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
  
 7. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE
 GAS SYSTEM OR PLACE A NOTE ON SET OF PLANS LISTING THE
 SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT
 WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC
 FG SEC. 402.3.
  
 8. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
  
 9. PROVIDE THE SIGNATURE OF ALL INFORMATION OF DATA
 SHALL BEAR THE PRINTED NAME OF THE SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  