Plan Review Notes
Plan Review Notes For Permit 20090271
Permit Number 20090271
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-04 07:25:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND SPEED FOR THIS PROJECT IS SPECIFIED AS 175
 MPH ON THE DRAWINGS AND CALCULATIONS. THE ACTUAL WIND
 SPEED IS 170 MPH VULT. USING THIS LOWER WIND SPEED
 SHOULD LOWER THE REQUIRED OPENING PRESSURES. FBC1609
  
 2) THE DESIGN PRESSURE CALCULATIONS USED ASCE 7-16.
 THIS EDITION OF ASCE IS NOT REFERENCED IN THE CURRENT
 CODE (2017 FBC). PLEASE USE ASCE 7-10 TO DETERMINE THE
 OPENING PRESSURES. FBC CHAPTER 35
  
 3) IN THE SCHEDULE ON SHEET A-1, THE COLUMN WITH THE
 PRESSURES REQUIRED FOR THE SPECIFIC OPENINGS DO NOT
 MATCH THE PRESSURES THAT ARE IN THE CLOUDED AREAS ON
 THE DETAILED ELEVATIONS. PLEASE COORDINATE. FBC 107.2
  
 4) THE POSITIVE PRESSURE IN THE CLOUDED AREA ON THE
 DETAILED ELEVATION FOR OPENING #7 IS +102.3 PSF AND THE
 PRESSURE IN THE SCHEDULE FROM THE PRODUCT APPROVAL IS
 +80 PSF. THIS DOES NOT MEET THE REQUIRED OPENING
 PRESSURE. PLEASE CORRECT. FBC 107.2 & 1609