Plan Review Notes For Permit 20090271 |
Permit Number |
20090271 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-02 11:30:39 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY D. | | PLEASE REVISE DESIGN PARAMETERS ON SHEET A-1. FBC | | 1609.4 | | | | 2) THE OPENING PRESSURES APPEAR TO BE LOW FOR A | | BUILDING IN EXPOSURE CATEGORY D WITH 170 MPH VULT WIND | | SPEED AND A ROOF HEIGHT OF 250'. SPECIFY THE WALL ZONE | | FOR EACH OF THE OPENINGS. PROVIDE THE CALCULATIONS THAT | | WERE USED TO DETERMINE THE OPENING PRESSURES OR THE | | WIND TUNNEL TEST REPORT. FBC 107 & 1609 | | | | 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER | | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE | | TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS | | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN | | PRESSURES FOR EACH OF THE DIFFERENT WINDOWS (GLASS | | TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. | | | | 4) CIRCLE OR HI- LIGHT THE APPROPRIATE ITEMS (SUCH AS | | SIZE, GLASS TYPE, DESIGN PRESSURE, ETC.) IN THE PRODUCT | | APPROVAL FOR THE WINDOWS, DOORS AND MULLIONS. FBC 107 |
|