Plan Review Notes
Plan Review Notes For Permit 20090271
Permit Number 20090271
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-02 11:30:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE CATEGORY D.
 PLEASE REVISE DESIGN PARAMETERS ON SHEET A-1. FBC
 1609.4
  
 2) THE OPENING PRESSURES APPEAR TO BE LOW FOR A
 BUILDING IN EXPOSURE CATEGORY D WITH 170 MPH VULT WIND
 SPEED AND A ROOF HEIGHT OF 250'. SPECIFY THE WALL ZONE
 FOR EACH OF THE OPENINGS. PROVIDE THE CALCULATIONS THAT
 WERE USED TO DETERMINE THE OPENING PRESSURES OR THE
 WIND TUNNEL TEST REPORT. FBC 107 & 1609
  
 3) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT WINDOWS (GLASS
 TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 4) CIRCLE OR HI- LIGHT THE APPROPRIATE ITEMS (SUCH AS
 SIZE, GLASS TYPE, DESIGN PRESSURE, ETC.) IN THE PRODUCT
 APPROVAL FOR THE WINDOWS, DOORS AND MULLIONS. FBC 107