Plan Review Notes
Plan Review Notes For Permit 20090264
Permit Number 20090264
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-13 16:01:21WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090264
 ADD: 5600 N. FLAGLER DR. # 606
 CONT: LEGACY BROTHERS CONSTRUCTION
 TEL: 912-657-5758
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. SEPT. 13TH/2020
 ACTION: DENIED
  
 1A) DISCREPANCY IN THE FLOOR PLAN SUBMITTED, SCOPE OF
 WORK AND THE UPLOADED FILES. THE FLOOR PLAN SHOWS IN
 THE MASTER BATH A TUB AND A ? BATH WITH A LAVATORY AND
 WATER CLOSET. THE SCOPE OF WORK INDICATES THE REPLACE
 TUB FOR NEW, BUT THE FILE UPLOADED SHOWS A NEW SHOWER
 PAN BASE. ADDITIONAL INFORMATION IS REQUIRED.107.2.1.2.
  
 1B) IF THERE IS A CHANGE FROM A TUB TO A SHOWER WILL
 THE SAME WASTE BE USED, OR WILL THERE BE A NEW HOLE
 CORED THROUGH THE FLOOR? IF THERE IS TO BE A NEW HOLE
 BORED THROUGH THE FLOOR THE FLOOR WILL NEED TO BE
 X-RAYED TO SEE THE LOCATION OF THE POST-STRESSED
 CABLES.
  
 1C) FOR A NEW PENETRATION THROUGH THE FLOOR SLAB PLEASE
 PROVIDE THE THROUGH PENETRATION FIRE STOP SYSTEM IN
 COMPLIANCE WITH THE 2017 FBC-B SECTION 714.4.1.1.
  
 1D) PLEASE ALSO PROVIDE WHAT TYPE OF PLEASE PROVIDE THE
 THROUGH PENETRATION FIRE STOP SYSTEM WILL BE USED IN
 THE OLD HOLE LEFT BY THE OLD DRAIN LINE. 2017 FBC-B
 SECTION 714.4.1.1.
  
 1E) IN EITHER CASE TUB OR SHOWER PLEASE PROVIDE WHAT
 TYPE OFF BACKER BOARD WILL BE INSTALLED ON EITHER THE
 SHOWER OR TUB. 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  