2020-09-12 12:42:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. IT IS NOT CLEAR HOW/WHERE THE MULLION WILL BE
 INSTALLED. BASED ON THE FLOOR PLAN IT APPEARS THAT THE
 WINDOWS WILL BE INSTALLED IN A CORNER, 90 DEGREE ANGLE.
 IF THE MULLION IS TO BE THE SUPPORT IN THE CORNER FOR
 BOTH WINDOWS, INDICATE ON THE PRODUCT APPROVAL WHERE
 THIS INSTALLATION IS INCLUDED IN THE NOA. IF IT IS NOT
 IN THE NOA, SITE SPECIFIC ENGINEERING IS REQUIRED, FBC
 R 301.
  
  