2020-09-28 07:34:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER THAT IS ON THE PRECAST GENERATOR SLAB
 AND ANCHORING PLANS, RONALD H. WILSON P.E. LICENSE NO.
 9710, HAS HAD HIS FL ENGINEERING LICENSE REVOKED SINCE
 2/28/2017. SUBMIT SIGNED AND SEALED GENERATOR PAD
 DRAWINGS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 ANY OPENINGS INTO THE BUILDING. FBC-R303.5
  
 3) THIS PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA, "AE" 7 FT NAVD88. THE GERERATOR IS REQUIRED TO BE
 LOCATED AT OR ABOVE THE FINISH FLOOR ELEVATION OF THE
 LOWEST OCCUPIABLE FLOOR OF THE RESIDENCE. FBC-R322.1.6