2020-12-17 09:42:47 | PLAN REVIEW / NFIP |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| CITY ORDINANCE NO. 4658-16 |
| |
| 3RD REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| |
| RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC) |
| |
| 1. REF. LINE A5 OF EC. LATITUDE IS STATED AS 39 33 81 |
| N. GOOGLE MAPS/GOOGLE EARTH SHOWS THE LATITUDE FOR 6175 |
| S FLAGLER AS 26 39 24 N. PLEASE CORRECT LATITUDE. |
| CORRECTED |
| |
| |
| 2. ORIGINAL SIGNATURE OF SURVEYOR IS REQUIRED. (NOT |
| CORRECTED) |
| |
| A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE |
| IS NOT CONSIDERED A DIGITAL SIGNATURE. |
| |
| EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR DROP |
| OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL WET |
| SEAL AND SIGNATURE TO: |
| |
| BUILDING DIVISION, FIRST FLOOR |
| CITY OF WEST PALM BEACH |
| 401 CLEMATIS ST |
| WEST PALM BEACH, FL 33401 |
| |
| NEW COMMENTS: |
| |
| 3. . FLOOD VENTS SHALL BE INSTALLED ON ADJACENT WALLS |
| OF ENCLOSED AREAS. SUBMIT NEW PLAN PAGES THAT SHOW THE |
| LOCATION OF THE VENTS. |
| R322.2.2.1INSTALLATION OF OPENINGS. T |
| THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS |
| INSTALLED SUCH THAT: |
| 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON |
| DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING |
| HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD |
| ELEVATION, EACH AREA SHALL HAVE OPENINGS. |
| 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN |
| 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR |
| GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE |
| IMMEDIATELY UNDER EACH OPENING. |
| 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN |
| DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED |
| OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION. |
| ALSO SEE SEC. 4.1 OF THE ICC-ES REPORT FOR VENT |
| LOCATION. |
| ALSO SEE FEMA TECHNICAL BULLETIN #1 - FLOOD OPENINGS IN |
| WALLS. |
| |
| NOTICE: PROVIDE BUILDING UNDER CONSTRUCTION ELEVATION |
| CERTIFICATE TO CITY INSPECTOR AT PLACEMENT OF 1ST |
| FLOOR. |
| PROVIDE FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| PRIOR TO C/O. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |