2020-12-17 09:04:43PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROVISO: GENERATOR SHALL BE BY SEPERATE PERMIT.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1. ALL PLAN SHEETS HAVE AN INCORRECT ADDRESS. (101
 SANTA LUCIA DRIVE). THE CORRECT ADDRESS IS 6175 S
 FLAGLER DRIVE. PLEASE CORRECT AND RE-SUBMIT. (NOT
 CORRECTED)
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE ICC-ES REPORT AND PRODUCT APPROVALS FOR
 SMART VENTS. (ICC-ES REPORT RCV'D. PROVIDE INSTALLATION
 INSTRUCTIONS FOR SMART VENT MODEL 1540-511).
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NEW COMMENTS:
  
 3. REFERENCE YOUR PERMIT REVIEW RESPONSE LTR DATED
 12/11/2020: ALTHOUGH MULTIPLE DOCUMENTS SUCH AS PRODUCT
 APPROVALS, NOC, SOILS REPORT, ETC. MAY BE UPLOADED AS
 ONE PDF, THE ELEVATION CERTIFICATE MUST BE UPLOADED
 SEPERATELY. WE HAVE TO SUBMIT THESE TO FEMA AND NEED A
 CLEAN EC WITHOUT ANY ATTACHMENTS.
 ALSO, PLEASE FOLLOW THE FILE NAMING GUIDELINES ON THE
 QUICK START GUIDE AND PROVIDE THE NAME OF THE DOCUMENTS
 INCLUDED IN THE FILE.
 IT'S PREFERABLE BUT NOT REQUIRED FOR EACH DOCUMENT TO
 BE UPLOADED SEPERATELY WITH IT'S APPROPRIATE NAME. THIS
 HELPS THE REVIEW PROCESS TREMENDOUSLY.
  
 4. I DO NOT SEE A NEW SURVEY IN THE RESPONSE LTR DOC.
 THE SURVEY SHOULD ALSO BE UPLOADED AS A SEPERATE FILE.
  
 5. FLOOD VENTS SHALL BE INSTALLED ON ADJACENT WALLS.
 SUBMIT NEW PLAN PAGES THAT SHOW THE LOCATION OF THE
 VENTS.
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
 ALSO SEE SEC. 4.1 OF THE ICC-ES REPORT FOR VENT
 LOCATION.
 ALSO SEE FEMA TECHNICAL BULLETIN #1 - FLOOD OPENINGS IN
 WALLS.
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  