Plan Review Notes
Plan Review Notes For Permit 20090239
Permit Number 20090239
Review Stop B
Sequence Number 2
Notes
Date Text
2020-12-01 16:57:34PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROVISO: GENERATOR SHALL BE BY SEPERATE PERMIT.
  
 1. ALL PLAN SHEETS HAVE AN INCORRECT ADDRESS. (101
 SANTA LUCIA DRIVE). THE CORRECT ADDRESS IS 6175 S
 FLAGLER DRIVE. PLEASE CORRECT AND RE-SUBMIT.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE ICC-ES REPORT AND PRODUCT APPROVALS FOR
 SMART VENTS.
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  