2020-09-23 09:51:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SMOKE/CO ALARMS MISSING ON FIRST FLOOR R314, R315
 (BEDROOM, BY STAIRWAY)
  
 2) SECOND FLOOR ALARMS MISSING IN HALLWAYS THAT HAVE
 HEADERS SEPARATING THE BEDROOM FROM OUTSIDE THE BEDROOM
 ALARMS.
  
 3) PANTRY SHOWS NO OUTLETS, MUD ROOM HAS COUNTER SPACE
 ALSO 210.52(C)
  
 4) SITTING ROOM HAS WALL THAT IS 2' NEEDS OUTLET
  
 5) GAME ROOM HAS WALLS NEEDING OUTLETS., SLIDING DOORS
 HAS WALL SPACE.
  
  