Plan Review Notes
Plan Review Notes For Permit 20090239
Permit Number 20090239
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-24 10:50:51PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT.
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 2. STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZRD AREA
 (SFHA). ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 (DFE) REQUIRE FLOOD OPENINGS. LOCATE THE REQUIRED
 NUMBER OF FLOOD OPENINGS ON THE FOUNDATION PLAN.
 FBC APPENDIX G FLOOD RESISTANT CONSTRUCTION AND
 FBC R 322.2.2 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
  
 3. PROVIDE THE ICC EVALUATION SERVICE REPORT FOR THE
 PROPOSED ICYNENE SPRAY FOAM INSULATION.
 DESIGNER SHALL SELECT THE PRODUCT TO BE INSTALLED TO
 ACHIEVE THE REQUIRED R-20 INSULATION VALUE FOR THE ROOF
 ASSEMBLY.
 PROVIDE THE ICYNENE SPRAY FOAM INSULATION INSTALLATION
 INSTRUCTIONS.
 INSTALLATION INSTRCUTIONS SHALL BE MADE AVAILABLE TO
 THE CITY INSPECTOR FOR INSPECTION.
  
 4. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 5. PRODUCT APPROVAL FL16546-R5 IS EXPIRED. PROVIDE
 PRODUCT APPROVAL BASED ON THE FBC 6TH EDITION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE OHD SUBMITTALS.
  
 6. DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  