2020-09-25 10:55:232ND REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20090229
 9/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS #2, 4, 8, & 9 FROM THE 1ST REVIEW LISTED BELOW
 STILL EXIST- PLEASE COMPLY. PLEASE NOTE A SEPARATE
 PERMIT IS REQUIRED FOR THE GAS PIPING INSTALLATION- SEE
 GAS REVIEW NOTES- 9/14/2020.
  
 2) PLUMBING SCOPE OF WORK NOTE 1: PROVIDE A FLAT LINE
 DRAWING THE LOCATION OF THE REPLACED CAST IRON FROM THE
 HOUSE TO THE CITY UTILITY CONNECTION INCLUDING THE TYPE
 AND SIZE OF PIPE, BURIAL DEPTH AND LOCATION OF REQUIRED
 CLEANOUTS AT THE HOUSE DRAIN /SEWER CONNECTION-
 SECTIONS P3002.2 & P3005.2.3 FBC RES.
  
 4) PLUMBING SCOPE OF WORK NOTE 6: PROVIDE WATER SUPPLY
 AND SANITARY RISER DRAWINGS FOR THE NEW SHOWER- SECTION
 107.3.5.3 WPB. PLEASE INCLUDE A SHOWER PAN DETAIL PER
 SECTION P2709.1 & P2709.2 FBC RES.
  
 8) BUILDING DEPARTMENT RECORDS DO NOT INDICATE A RECENT
 PERMIT FOR A GAS WATER HEATER IN THE GARAGE AND THE PB
 PROPERTY APPRAISER'S REPORT INDICATES A FINISHED
 GARAGE. AS NOTED IN COMMENT #1 A SEPARATE PERMIT AND
 PLANS WILL BE REQUIRED FOR INSTALLATION OF THE GAS
 PIPING TO THE WATER HEATER. UNLESS EVIDENCE IS PROVIDED
 TO INDICATE THE EXISTING GAS WATER HEATER WAS INSTALLED
 WITH A PERMIT, THE PLANS SHALL INDICATE A NEW
 INSTALLATION AND THE REQUIRED GAS RISER DRAWING SHALL
 SHOW THE COMPLETE GAS PIPING SYSTEM FOR THE RESIDENCE.
 COMBUSTION AND VENTING PLANS SHALL ALSO BE REQUIRED-
 SECTION 107.1 & 107.3.5.3 WPB.
  
 9) PLEASE CLARIFY IF THE NAVIEN NPE AT 11.2 GPM HOT
 WATER SUPPLY CAPACITY IS SIZED FOR THE ENTIRE
 RESIDENCE. PROVIDE A LIST OF FIXTURES TO BE SUPPLIED BY
 THE UNIT AND THE TOTAL GPM FLOW REQUIRED- SECTIONS
 G2448.1 & P2903.1 FBC RES. SHOW HOW CONDENSATE FOR THE
 HEATER WILL BE DRAINED AND DOSCHARGED TO THE EXTERIOR
 OF THE BUILDING- SECTION R318.5 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  