2020-09-25 10:55:23 | 2ND REVIEW FBC-2017 RES. PLUMBING |
| PERMIT- 20090229 |
| 9/25/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS #2, 4, 8, & 9 FROM THE 1ST REVIEW LISTED BELOW |
| STILL EXIST- PLEASE COMPLY. PLEASE NOTE A SEPARATE |
| PERMIT IS REQUIRED FOR THE GAS PIPING INSTALLATION- SEE |
| GAS REVIEW NOTES- 9/14/2020. |
| |
| 2) PLUMBING SCOPE OF WORK NOTE 1: PROVIDE A FLAT LINE |
| DRAWING THE LOCATION OF THE REPLACED CAST IRON FROM THE |
| HOUSE TO THE CITY UTILITY CONNECTION INCLUDING THE TYPE |
| AND SIZE OF PIPE, BURIAL DEPTH AND LOCATION OF REQUIRED |
| CLEANOUTS AT THE HOUSE DRAIN /SEWER CONNECTION- |
| SECTIONS P3002.2 & P3005.2.3 FBC RES. |
| |
| 4) PLUMBING SCOPE OF WORK NOTE 6: PROVIDE WATER SUPPLY |
| AND SANITARY RISER DRAWINGS FOR THE NEW SHOWER- SECTION |
| 107.3.5.3 WPB. PLEASE INCLUDE A SHOWER PAN DETAIL PER |
| SECTION P2709.1 & P2709.2 FBC RES. |
| |
| 8) BUILDING DEPARTMENT RECORDS DO NOT INDICATE A RECENT |
| PERMIT FOR A GAS WATER HEATER IN THE GARAGE AND THE PB |
| PROPERTY APPRAISER'S REPORT INDICATES A FINISHED |
| GARAGE. AS NOTED IN COMMENT #1 A SEPARATE PERMIT AND |
| PLANS WILL BE REQUIRED FOR INSTALLATION OF THE GAS |
| PIPING TO THE WATER HEATER. UNLESS EVIDENCE IS PROVIDED |
| TO INDICATE THE EXISTING GAS WATER HEATER WAS INSTALLED |
| WITH A PERMIT, THE PLANS SHALL INDICATE A NEW |
| INSTALLATION AND THE REQUIRED GAS RISER DRAWING SHALL |
| SHOW THE COMPLETE GAS PIPING SYSTEM FOR THE RESIDENCE. |
| COMBUSTION AND VENTING PLANS SHALL ALSO BE REQUIRED- |
| SECTION 107.1 & 107.3.5.3 WPB. |
| |
| 9) PLEASE CLARIFY IF THE NAVIEN NPE AT 11.2 GPM HOT |
| WATER SUPPLY CAPACITY IS SIZED FOR THE ENTIRE |
| RESIDENCE. PROVIDE A LIST OF FIXTURES TO BE SUPPLIED BY |
| THE UNIT AND THE TOTAL GPM FLOW REQUIRED- SECTIONS |
| G2448.1 & P2903.1 FBC RES. SHOW HOW CONDENSATE FOR THE |
| HEATER WILL BE DRAINED AND DOSCHARGED TO THE EXTERIOR |
| OF THE BUILDING- SECTION R318.5 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |