Plan Review Notes
Plan Review Notes For Permit 20090229
Permit Number 20090229
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-14 09:26:221ST REVIEW FBC-2017 RES. PLUMBING
  
 PERMIT- 20090229
  
 9/14/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
  
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
  
 FS- FLORIDA STATUTES
  
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMITS: THE MAIN APPLICATION SUBMITTED BY GC D'
 ANGELO BUILDERS INC. HAS THE PLUMBING TRADE BOX CHECKED
 OFF, NOT THE STRUCTURAL, AND THERE IS NO WORK
 DESCRIPTION SHOWN. PLEASE PROVIDE A COMPLETE
 APPLICATION AND A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB AMENDMENTS TO THE FBC-17. PLEASE NOTE
 THAT A SEPARATE PERMIT AND PLAN IS REQUIRED FOR THE GAS
 WATER HEATER INSTALLATION- SEE COMMENT # 8 BELOW.
  
 2) PLUMBING SCOPE OF WORK NOTE 1: PROVIDE A FLAT LINE
 DRAWING THE LOCATION OF THE REPLACED CAST IRON FROM THE
 HOUSE TO THE CITY UTILITY CONNECTION INCLUDING THE TYPE
 AND SIZE OF PIPE, BURIAL DEPTH AND LOCATION OF REQUIRED
 CLEANOUTS AT THE HOUSE DRAIN /SEWER CONNECTION-
 SECTIONS P3002.2 & P3005.2.3 FBC RES.
  
 3) PLUMBING SCOPE OF WORK NOTES 2 & 3: THE COST VALUES
 OF OWNER SUPPLIED FIXTURES SHALL BE ADDED INTO THE
 TOTAL COST OF THE PROJECT- SECTION 109.3 WPB. PROVIDE A
 COPY OF THE CONTRACT AND A ITEMIZED COST BREAKDOWN THAT
 INCLUDES ALL LABOR, MATERIALS, FIXTURES AND EQUIPMENT.
  
 4) PLUMBING SCOPE OF WORK NOTE 6: PROVIDE WATER SUPPLY
 AND SANITARY RISER DRAWINGS FOR THE NEW SHOWER- SECTION
 107.3.5.3 WPB.
  
 5) BATHROOM DRAWING: PROVIDE THE TYPE OF NON-ABSORBENT
 FINISH MATERIAL TO BE INSTALLED ON THE SHOWER WALLS UP
 TO A MINIMUM HEIGHT OF 6 FT.- SECTIONS P2710.1 & R307.2
 FBC RES.
  
 6) BATHROOM DRAWING: PLACE A NOTE ON THE PLAN VERIFYING
 THE EXISTING WINDOW GLAZING IN THE SHOWER SURROUND
 MEETS THE CURRENT SAFETY GLAZING STANDARD AS REQUIRED
 BY SECTION R308.1 FBC RES.
  
 7) BATHROOM DRAWING: CLARIFY IF A GLASS SHOWER DOOR
 WILL BE INSTALLED AND SHOW THE LOCATION AND SIZE OF
 OPENING- SECTION P2708.1.1 FBC RES. PLEASE ADD THE COST
 OF THE DOOR TO THE TOTAL COST OF THE PROJECT IF
 APPLICABLE.
  
 8) BUILDING DEPARTMENT RECORDS DO NOT INDICATE A RECENT
 PERMIT FOR A GAS WATER HEATER IN THE GARAGE AND THE PB
 PROPERTY APPRAISER'S REPORT INDICATES A FINISHED
 GARAGE. AS NOTED IN COMMENT #1 A SEPARATE PERMIT AND
 PLANS WILL BE REQUIRED FOR INSTALLATION OF THE GAS
 PIPING TO THE WATER HEATER. UNLESS EVIDENCE IS PROVIDED
 TO INDICATE THE EXISTING GAS WATER HEATER WAS INSTALLED
 WITH A PERMIT, THE PLANS SHALL INDICATE A NEW
 INSTALLATION AND THE REQUIRED GAS RISER DRAWING SHALL
 SHOW THE COMPLETE GAS PIPING SYSTEM FOR THE RESIDENCE.
 COMBUSTION AND VENTING PLANS SHALL ALSO BE REQUIRED-
 SECTION 107.1 & 107.3.5.3 WPB.
  
 9) PLEASE CLARIFY IF THE NAVIEN NPE AT 11.2 GPM HOT
 WATER SUPPLY CAPACITY IS SIZED FOR THE ENTIRE
 RESIDENCE. PROVIDE A LIST OF FIXTURES TO BE SUPPLIED BY
 THE UNIT AND THE TOTAL GPM FLOW REQUIRED- SECTIONS
 G2448.1 & P2903.1 FBC RES. SHOW HOW CONDENSATE FOR THE
 HEATER WILL BE DRAINED AND DOSCHARGED TO THE EXTERIOR
 OF THE BUILDING- SECTION R318.5 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
  
 MECHANICAL/PLUMBING PLANS EXAMINER
  
 401 CLEMATIS STREET
  
 WEST PALM BEACH FL 33401
  
 561-805-6719
  
 [email protected]
  
  
  