| 1ST REVIEW FBC-2017 RES. PLUMBING |
| PERMIT- 20090208 |
| 9/14/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| |
| FS- FLORIDA STATUTES |
| |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION MANUAL FOR THE NEW TANKLESS WATER HEATER |
| SUPPLYING THE CABANA FIXTURES- SECTION G2448.1 M2005.1 |
| FBC RES. THE SPECS SHALL INDICATE THE HOT WATER GPM |
| CAPACITY OF THE UNIT BASED ON THE MANUFACTURER?S |
| TEMPERATURE RISE CHART; AND SHALL SHOW THE EFFICIENCY |
| RATING OF THE UNIT- SEE TABLE C404.2 FBC EC. PLEASE |
| INCLUDE A LIST OF FIXTURES TO BE SUPPLIED BY THE WATER |
| HEATER. |
| |
| 2) PROVIDE A BASIC ELEVATION PLAN DETAIL SHOWING THE |
| MOUNTING LOCATION OF THE WATER HEATER AND CLEARANCE |
| DISTANCES FROM GRADE, OVERHEAD CONSTRUCTION, AND |
| OPERABLE OPENINGS INTO THE BUILDING- SECTION G2448.1. |
| PROVIDE A NOTE OR DETAIL TO INDICATE THAT CONDENSATE |
| FOR THE HEATER WILL DISCHARGE A MINIMUM OF 1FT. FROM |
| THE BUILDING- SECTION R318.5. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |