Plan Review Notes
Plan Review Notes For Permit 20090208
Permit Number 20090208
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-14 11:05:19 
 1ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20090208
 9/14/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
  
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
  
 FS- FLORIDA STATUTES
  
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE NEW TANKLESS WATER HEATER
 SUPPLYING THE CABANA FIXTURES- SECTION G2448.1 M2005.1
 FBC RES. THE SPECS SHALL INDICATE THE HOT WATER GPM
 CAPACITY OF THE UNIT BASED ON THE MANUFACTURER?S
 TEMPERATURE RISE CHART; AND SHALL SHOW THE EFFICIENCY
 RATING OF THE UNIT- SEE TABLE C404.2 FBC EC. PLEASE
 INCLUDE A LIST OF FIXTURES TO BE SUPPLIED BY THE WATER
 HEATER.
  
 2) PROVIDE A BASIC ELEVATION PLAN DETAIL SHOWING THE
 MOUNTING LOCATION OF THE WATER HEATER AND CLEARANCE
 DISTANCES FROM GRADE, OVERHEAD CONSTRUCTION, AND
 OPERABLE OPENINGS INTO THE BUILDING- SECTION G2448.1.
 PROVIDE A NOTE OR DETAIL TO INDICATE THAT CONDENSATE
 FOR THE HEATER WILL DISCHARGE A MINIMUM OF 1FT. FROM
 THE BUILDING- SECTION R318.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
  
 MECHANICAL/PLUMBING PLANS EXAMINER
  
 401 CLEMATIS STREET
  
 WEST PALM BEACH FL 33401
  
 561-805-6719
  
 [email protected]
  
  