2020-09-12 09:02:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20090208
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW ON DRAWING THE METHOD USED TO SIZE THIS
 NATURAL GAS SYSTEM. FBC FG 402.4
  
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017
 FBC RES. SEC. G2408.1.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 4) PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 5) SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC FG SEC.304.9.3 OR 2017 FBC RES. SEC. G2407.9.3.
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 7) GAS TABLE NUMBER IN PARENTHESIS FOR THE 12?
 W.C./INTERIOR IS BLURRED AND I CAN?T READ IT. PLEASE
 REWRITE THIS NUMBER. FBC FS 107.2.1
  
  
 8) PLEASE CHECK THE TABLES USED FOR THE 12? W.C.
 INTERIOR PIPING TABLE 402.4 (17) IS FOR NATURAL GAS;
 LESS THAN 2 PSI; PRESSURE DROP 6.0IN W.C.; SPECIFIC
 GRAVITY 0.60. PLEASE MAKE SURE THE PRESSURE DROP IS THE
 SAME FOR EACH TABLE FOR EACH MATERIAL USED. FBC FG 402
  
 9) PLEASE SHOW OUTLET PRESSURES FOR EACH MP REGULATOR
 IN THIS SYSTEM. FBC FG 410.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  