2020-09-09 16:35:59 | 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT- 20090171 |
| 9/9/2020 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE NEW ACCESSIBLE SHUT OFF VALVE FOR THE RANGE |
| SHALL BE LOCATED NO MORE THAN 6 FT. FROM THE APPLIANCE- |
| SECTION 409.5.1 FBC FG. |
| |
| 2) SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF VALVE |
| FOR THE SYSTEM AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS- SECTION 10.4 NFPA 96. |
| |
| 10.4.1- UPON ACTUATION OF ANY FIRE-EXTINGUISHING SYSTEM |
| FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND |
| ELECTRIC POWER THAT PRODUCE HEAT TO ALL EQUIPMENT |
| PROTECTED BY THE SYSTEM SHALL AUTOMATICALLY SHUT OFF. |
| |
| 3) THE GAS RANGE IS INDICATED AS EXISTING UNDER THE |
| APPROVED PLANS FOR THE COMMERCIAL RENOVATION PROJECT |
| UNDER PERMIT 20010838, HOWEVER I AM NOT ABLE TO LOCATE |
| A PERMIT FOR THE RANGE OR A PERMIT FOR ANY OTHER GAS |
| PIPING. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| THE RANGE- SECTION 623.1 FBC FG. |
| |
| 4) CLARIFY IF THE GAS RANGE IS THE ONLY GAS-FIRED |
| APPLIANCE BEING SERVED BY THE EXISTING METER. IF THERE |
| ARE OTHER GAS-FIRED EQUIPMENT OR APPLIANCES BEING |
| SERVED BY THE METER, THEN THE ISOMETRIC DRAWING MUST BE |
| MODIFIED TO SHOW THE ENTIRE GAS PIPING SYSTEM INCLUDING |
| THE LONGEST RUN LENGTH AND BRANCH PIPING LENGTHS, |
| INDIVIDUAL AND TOTAL BTUH LOADS OF APPLIANCES OR |
| EQUIPMENT, TYPES AND SIZES OF PIPING, LOCATIONS OF |
| REGULATORS AND SHUTOFF VALVES- SECTION 401.4 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |