2020-09-09 16:35:591ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20090171
 9/9/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW ACCESSIBLE SHUT OFF VALVE FOR THE RANGE
 SHALL BE LOCATED NO MORE THAN 6 FT. FROM THE APPLIANCE-
 SECTION 409.5.1 FBC FG.
  
 2) SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF VALVE
 FOR THE SYSTEM AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 10.4 NFPA 96.
  
 10.4.1- UPON ACTUATION OF ANY FIRE-EXTINGUISHING SYSTEM
 FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND
 ELECTRIC POWER THAT PRODUCE HEAT TO ALL EQUIPMENT
 PROTECTED BY THE SYSTEM SHALL AUTOMATICALLY SHUT OFF.
  
 3) THE GAS RANGE IS INDICATED AS EXISTING UNDER THE
 APPROVED PLANS FOR THE COMMERCIAL RENOVATION PROJECT
 UNDER PERMIT 20010838, HOWEVER I AM NOT ABLE TO LOCATE
 A PERMIT FOR THE RANGE OR A PERMIT FOR ANY OTHER GAS
 PIPING. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE RANGE- SECTION 623.1 FBC FG.
  
 4) CLARIFY IF THE GAS RANGE IS THE ONLY GAS-FIRED
 APPLIANCE BEING SERVED BY THE EXISTING METER. IF THERE
 ARE OTHER GAS-FIRED EQUIPMENT OR APPLIANCES BEING
 SERVED BY THE METER, THEN THE ISOMETRIC DRAWING MUST BE
 MODIFIED TO SHOW THE ENTIRE GAS PIPING SYSTEM INCLUDING
 THE LONGEST RUN LENGTH AND BRANCH PIPING LENGTHS,
 INDIVIDUAL AND TOTAL BTUH LOADS OF APPLIANCES OR
 EQUIPMENT, TYPES AND SIZES OF PIPING, LOCATIONS OF
 REGULATORS AND SHUTOFF VALVES- SECTION 401.4 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  