2020-09-08 09:28:30 | 09/08/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE COOK TO NEED TO BE FULL LOAD, IT IS LABELED AT |
| 18 BTU'S AND THERE IS 6 BURNERS AND A GRILL EACH AT 18 |
| X 7 EQUALS 126 BTU'S PLEASE CHANGE AND RECALCULATE FOR |
| SIZING IF NEEDED PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. PLEASE LABEL THE TYPE OF PIPE MATERIAL BEING |
| INSTALLED AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. PLEASE LABEL THE TYPE OF GAS (LP OR NATURAL) PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 5. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND |
| THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| SEC. G2421.1. |
| |
| 6. POOL HEATER IS MISSED LABELED AT 440 BTU'S AND SPECS |
| SAYS 400 BTU'S PLEASE CORRECT PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR (DRYER SHOW |
| LOCATION, IF IN CLOSET ARE LOUVER BEING USED, AND |
| RANGE) GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED |
| BY THE BUILDING'S MECHANICAL VENTILATION SYSTEM, THE |
| SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE |
| IN ADDITION TO THE REQUIRED VENTILATION AIR PER THE |
| 2017 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR |
| AND VENTILATION AIR SYSTEM. |
| |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| |
| 9. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS OF THE GAS VENT(S) FOR THE TANKLESS HEATER |
| INSIDE PER THE 2017 FBC RES. SECS. G2426 THRU G2429.1. |
| |
| 11. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER |
| A ROOF PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| |
| 12. IF THE GAS GRILL IS IN A COVERED PATIO, AND A HOOD |
| IS REQUIRED A SEPARATE PERMIT FOR THE HOOD IS REQUIRED |
| PLEASE NOT ON PLANS PER THE 2017 FBC RES. SEC. G2408.1. |
| |
| 13. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| G2421.2. |
| |
| 14. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| THE 2017 FBC RES. SEC. G2401.1.3. |
| |
| 15. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED, |
| EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER |
| THE 2017 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2. |
| |
| 16. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR |
| THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND |
| LABELED PER THE 2017 FBC FG RES. SEC. G2404.3. THE |
| MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT |
| ARE BEING EXHAUSTED BY THE DRYER. |
| |
| 17. ON THE HOUSE PLAN SHOW THE LOCATION OF THE TANKLESS |
| WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |