2020-09-10 13:56:06 | 09/10/20 1ST PLUMBING REVISION REVIEW**DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON PAGE P-4 AN EXTRA P TRAP WAS ADDED TO S2 AND NOT |
| SHOWN ON THE ISOMETRIC DIAGRAM, PLEASE SHOW ON P-13 PER |
| THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 2. ON P-5 ITEM 15 THE NEW 3" WATER LINES TO MAIN HAVE |
| BEEN ADDED AND NOT CLOUDED AND OR NOT SHOW ON P-14 |
| ISOMETRIC, PLEASE SHOW PER THE WPB AMENDMENTS TO THE |
| FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. ON P-5 ITEM 16, PLEASE PROVIDE DETAIL OF THE TRASH |
| SHOOT AND A SUITABLE HAZARD BACKFLOW DEVICE PER TABLE |
| 608.1 OF THE 2017 PLUMBING CODE AND 608.13.3. PLEASE |
| SHOW THE DEVICE ON ISOMETRIC OF P-14 PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 4. ON P-11 DIAGRAM 2, THE LAST FLOOR SINK IS VENTED |
| WITH AN AIR ADMITTANCE VALVE WHICH IS NOT IN A SUITABLE |
| LOCATION UNLESS ACCES TO IT IS SHOWN OR POSSIBLE. |
| PLEASE PLEASE CLARIFY OR RE-VENT TO PB3 AND REMOVE THAT |
| SINK FROM DOWNSTREAM OF THE SYSTEM TO THE VENT FLOOR |
| SINK PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |