2020-09-07 12:43:26 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20090164 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-6: THE REVISION (7A) FOR RESPONSES IS DATED |
| 08/07/2020, THE REVISION (8) IS DATED 07/15/2020. THE |
| REVISION (7A) NOTE (10) HAS THE HUB DRAIN CLOUDED. |
| REVISION (8) NOTE (10) HAS THE HUB DRAIN REMOVED AND IS |
| NOW A FLOOR DRAIN, THIS CHANGE HAS NOT BEEN CLOUDED. |
| PLEASE INDICATE CORRECT DATES AND CLOUD CHANGES. FBC FS |
| 107.2.1 |
| |
| 2) SHEET M-6: FCU-1 CONDENSATE LINE HAS BEEN RELOCATED |
| BUT THERE IS NO CLOUD ON THE DRAWINGS SHOWING THIS IS A |
| CHANGE. PLEASE CORRECT AND MARK ALL CHANGES TO THIS |
| DRAWING WITH CLOUDS. FBC FS 107.2.1 |
| |
| 3) SHEET M-10: THE MUA-1 AND MUA-2 SUPPLY DUCT AND |
| KEF-1, CU-1 ALL HAVE BEEN ADJUSTED BUT NO CLOUDS ARE ON |
| THE DRAWINGS TO IDENTIFY THE CHANGES. PLEASE MAKE SURE |
| TO CLOUD ALL REVISIONS ON ALL SHEETS. FBC FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |