Plan Review Notes
Plan Review Notes For Permit 20090118
Permit Number 20090118
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-09-03 12:34:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEETS A 1.1 & 1.2 - DOORS N 185, 285, 385 AND 485
 ARE INDICATING THAT THEY OPEN BOTH INSWING AND OUTSWING
 INTO THE EXIT CORRIDOR. THESE DOUBLE SMOKE PARTITION
 DOORS ARE DIRECTLY OUSIDE THESE DOORS WITH THE DOOR
 CLOSET TO THIS NEW SPACE OPENING INTO THE EXIT TRAVEL
 PATH ON THE SIDE OF THE CORRIDOR. THE BATH DOOR OPEN
 INTO THAT EXIT TRAVEL PATH AND ENCROACHES ON THE EGRESS
 WIDTH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 BECAUSE THE EGRESS PATH OF THE CORRIDOR IS ON THE SAME
 SIDE OF THE BATH DOOR THAT OPENS INTO THE CORRIDOR, IT
 RESTRICTS THE EGRESS WITH. A PERSON CAN NOT OPEN THE
 OTHER CORRIDOR DOOR IN THAT PATH OF TRAVEL.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRTIVE.
  
  
  
  
 2) THERE ARE NO INDICATIONS OF FIRE DEVICES WITHIN THE
 ROOMS. FIRE ALARM DEVICES ARE REQUIRED WITHIN THE ROOMS
 AS THERE ARE NOW OCCUPIABLE BY THE GENRAL PUBLIC.
  
 PER NFPA 101, CH 33
  
 33.3.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
  
 33.3.3.4.4 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION
 SHALL BE
 PROVIDED AUTOMATICALLY, WITHOUT DELAY, BY INTERNAL
 AUDIBLE ALARM
 IN ACCORDANCE WITH 9.6.3.
  
 9.6.3 OCCUPANT NOTIFICATION.
 9.6.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED TO
 ALERT OCCUPANTS
 OF A FIRE OR OTHER EMERGENCY WHERE REQUIRED BY OTHER
 SECTIONS OF
 THIS CODE.
  
 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH
 9.6.3.5.8,
 NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE
 AUDIBLE, AND
 VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM
 AND SIGNALING CODE.
  
 THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 PLEASE CORRECT
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  