2020-09-14 08:33:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090099
 ADD: 205 N. DIXIE HWY. 5TH FLOOR.
 CONT: HEDRICK BROTHERS
 TEL: 561-578-1602
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 14TH/2020
 ACTION: BUILDING PROVISO
  
 1A SHEET FP1.05 SHOWS THE REMOVAL OF FIRE SPRINKLERS
 FROM THE IT ROOM. THIS TYPE OF ROOMS IS 1-HOUR FIRE
 RATES, THE PLANS DO NOT PROVIDE THE THROUGH
 -PENETRATION FIRESTOP SYSTEM FOR THE WHOLE WHEN THE 2 ?
 INCH SPRINKLER PIPE IS REMOVED. 2017 FBC-B SECTION
 714.3.1.2.
  
 1B) IF WALL SECTIONS ARE TO BE REMOVED THEN THE NEW
 WALL SECTIONS MUST MEET THE REQUIREMENTS OF 2017 FBC-B
 715.2 S FIRE-RESISTANT JOINT SYSTEM SHALL BE SECURELY
 INSTALLED IN ACCORDANCE WITH THE LISTING CRITERIA IN OR
 ON THE JOINT FOR ITS ENTIRE LENGTH SO AS NOT TO
 DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY TO
 ACCOMMODATE MOVEMENTS AND TO RESIST THE PASSAGE OF FIRE
 AND HOT GASES.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  
  
2020-09-14 07:39:00IN REVIEW, 9/14/ JW