2020-09-14 08:33:44 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20090099 |
| ADD: 205 N. DIXIE HWY. 5TH FLOOR. |
| CONT: HEDRICK BROTHERS |
| TEL: 561-578-1602 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. SEPT. 14TH/2020 |
| ACTION: BUILDING PROVISO |
| |
| 1A SHEET FP1.05 SHOWS THE REMOVAL OF FIRE SPRINKLERS |
| FROM THE IT ROOM. THIS TYPE OF ROOMS IS 1-HOUR FIRE |
| RATES, THE PLANS DO NOT PROVIDE THE THROUGH |
| -PENETRATION FIRESTOP SYSTEM FOR THE WHOLE WHEN THE 2 ? |
| INCH SPRINKLER PIPE IS REMOVED. 2017 FBC-B SECTION |
| 714.3.1.2. |
| |
| 1B) IF WALL SECTIONS ARE TO BE REMOVED THEN THE NEW |
| WALL SECTIONS MUST MEET THE REQUIREMENTS OF 2017 FBC-B |
| 715.2 S FIRE-RESISTANT JOINT SYSTEM SHALL BE SECURELY |
| INSTALLED IN ACCORDANCE WITH THE LISTING CRITERIA IN OR |
| ON THE JOINT FOR ITS ENTIRE LENGTH SO AS NOT TO |
| DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY TO |
| ACCOMMODATE MOVEMENTS AND TO RESIST THE PASSAGE OF FIRE |
| AND HOT GASES. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| |
| |
2020-09-14 07:39:00 | IN REVIEW, 9/14/ JW |