Plan Review Notes
Plan Review Notes For Permit 20090066
Permit Number 20090066
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-15 14:56:211ST REVIEW FBC-2017 RES.
 PERMIT- 20090066
 9/15/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
 A) THE SPECS SUBMITTED FOR THE GENERATOR INDICATE
 327,000 BTUH AT FULL LOAD. PLEASE NOTE THE UPDATED
 SPECS FOR GENERAC 22KW GENERATORS ARE LISTED AT 306
 BTUH AT FULL LOAD- SECTION G2413.2 FBC RES. AND SECTION
 107.2.1 WPB.
 B) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 C) PROVIDE THE EHD OF THE 3/4"TRAC PIPE- TABLE
 G2413.4(6) [402.4(18)]
 D) INDICATE ON THE RISER WHICH B42 REGULATOR MODEL WILL
 BE INSTALLED- MODEL R, N, OR H AND SUBMIT HIGHLIGHTED
 OR MARKED UP SPEC SHEETS SHOWING THE MAX INLET AND
 OUTLET SIZE AND PRESSURES, SPRING DATA, SPRING COLOR
 OUTLET PRESSURE RANGE AND ORIFICE SIZE- SECTION G2421.1
 & G2421.2.
 E) SHOW THE SHUTOFF VALVE FOR THE GAS SUPPLY TO THE
 GENERATOR, AND THE REQUIRED PIPE UNION AT THE
 REGULATOR- SECTIONS G2420.4, G2420.5, AND G2421.2(7).
 F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
 G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3
 H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 FLEX CONNECTOR AND TO THE SCHEDULE 40 METALLIC PIPE PER
 SECTIONS G2415.17.1 & G2415.17.2. PLEASE NOTE THAT
 SPECS FOR ANODELESS RISERS AND PE/METALLIC PIPE
 CONNECTORS SHALL BE LISTED AND LABELED.
 I) SHOW THE LOCATION OF THE DRIP LEG AT THE GENERATOR-
 SECTION G2419.2.
  
 2) PLEASE SUBMIT INSTALLATION GUIDELINES FROM GENERAC
 TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS
 SHOWN ON THE SURVEY ARE CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS- SECTION G2406.2 FBC RES.
  
 3) PLEASE PROVIDE A TITLE BLOCK WITH THE SIGNATURE ON
 THE DRAWING TO CLEARLY INDICATE THE LICENSED CONTRACTOR
 OR QUALIFIERS NAME AND LICENSE NUMBER- SECTION 107.2.1
 WPB.
  
 4) A SUB-PERMIT FOR THE GAS PIPING INSTALLATION IS
 REQUIRED- SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  