2020-09-14 17:15:58 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090061 |
| 9/14/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE GAS RISER DRAWING AND SURVEY INDICATE AN |
| EXISTING 500-GALLON LP TANK. I HAVE RESEARCHED THE |
| BUILDING DEPARTMENT RECORDS AND I CANNOT LOCATE A |
| PERMIT OR PLANS FOR THE TANK. AT THIS TIME THE TANK |
| WILL BE REVIEWED AS A NEW INSTALLATION PENDING EVIDENCE |
| IS PROVIDED TO INDICATE IT WAS PERMITTED AND INSPECTED |
| BY THE WPB BUILDING DEPARTMENT- SECTION 1005.1 & |
| 107.2.1 WPB AMENDMENTS TO THE FBC-17. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LP TANK |
| SHOWING THE TANK MEETS THE CURRENT TESTING, LISTING AND |
| COMPLIANCE STANDARDS IN ACCORDANCE WITH SECTION 5.2.1.1 |
| NFPA 58. |
| |
| 3) PROVIDE A SURVEY DRAWING MARKED UP TO SHOW THE |
| REQUIRED 10 FT. UG TANK CLEARANCE DISTANCES TO THE |
| HOUSE AND ADJACENT PROPERTY LINES- TABLE 6.3.1.1 NFPA |
| 58. PLEASE NOTE THAT IF THE TANK IS LESS THAN 10 FT. |
| FROM THE DRIVEWAY, THE SHELL FOR THE TANK SHALL BE 18 |
| IN. BELOW GRADE OR VEHICULAR BARRIER PROTECTION WILL BE |
| REQUIRED- SECTIONS 6.6.6.1 (A). (PLEASE NOTE THE |
| SUBMITTED SURVEY COPY FOR A RESIDENCE ON SOUTHWICK WAY |
| APPEARS TO BE SUBMITTED IN ERROR.) |
| |
| 4) THE GAS RISER DRAWING SHOWS AN INCOMPLETE ANCHORING |
| DETAIL FOR THE TANK. PLEASE PROVIDE ENGINEERING FOR |
| ANCHORING THE TANK TO PREVENT FLOTATION, COLLAPSE, OR |
| LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA 58. INCLUDE A |
| FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE BURIAL |
| DEPTH, TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| STRAPS. |
| |
| 5) THE TANK SHALL BE PROTECTED AGAINST CORROSION BY |
| INSTALLATION OF A CATHODIC PROTECTION SYSTEM CONSISTING |
| OF A SACRIFICIAL ANODE OR AN IMPRESSED CURRENT ANODE |
| PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA 58. INDICATE |
| THE TYPE OF PROTECTION AND HOW IT WILL BE TESTED- |
| SECTION 6.17.1 NFPA 58. |
| |
| 6) GAS ISOMETRIC DRAWING: |
| A) INDICATE THE PE PIPE SIZING TABLE ON THE DRAWING- |
| SEE TABLES G2413.4(1)- G2413.4(8) FBC RES. |
| B) INDICATE THE MAKES AND MODELS OF THE REGULATORS ON |
| THE DRAWING AND SUBMIT MANUFACTURER'S SPECIFICATIONS |
| MARKED UP TO SHOW THE INLET AND OUTLET SIZES AND |
| PRESSURES, AND ORIFICE SIZES- SECTION G2421.1 & G2421.2 |
| FBC RES. |
| C) SHOW THE SHUTOFF VALVE FOR THE GAS SUPPLY TO THE |
| GENERATOR, AND THE REQUIRED PIPE UNION AT THE |
| REGULATOR- SECTIONS G2420.4, G2420.5, AND G2421.2(7). |
| D) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| G2415.1. |
| E) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO |
| THE UG PE PIPING- SECTION G2415.17.3 |
| F) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE |
| FLEX CONNECTOR OR METALLIC PIPE PER SECTIONS G2415.17.1 |
| & G2415.17.2. PLEASE NOTE THAT SPECS FOR ANODELESS |
| RISERS AND PE/METALLIC PIPE CONNECTORS SHALL BE LISTED |
| AND LABELED. |
| G) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2 |
| FBC RES. |
| |
| 7) AS NOTED ABOVE AN INCORRECT SURVEY DRAWING HAS BEEN |
| SUBMITTED. PLEASE PROVIDE THE LOCATION OF THE GENERATOR |
| ON THE RE-SUBMITTED SURVEY WITH CLEARANCE DISTANCES TO |
| THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND |
| THE ADJACENT PROPERTY LINES- SECTION 107.2.1 WPB. |
| PLEASE ALSO SUBMIT INSTALLATION GUIDELINES FROM GENERAC |
| TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS |
| SHOWN ON THE SURVEY. |
| |
| 8) PLEASE PROVIDE A TITLE BLOCK WITH THE SIGNATURE ON |
| THE DRAWING TO CLEARLY INDICATE THE LICENSED CONTRACTOR |
| OR QUALIFIERS NAME AND LICENSE NUMBER- SECTION 107.2.1 |
| WPB. |
| |
| 9) A SUB-PERMIT FOR THE LP TANK AND GAS PIPING |
| INSTALLATIONS IS REQUIRED- SECTION 105.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |