2020-09-24 16:00:39 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY | | OPENINGS INTO A BUILDING AND THE SURVEY SHOWS THE | | GENERATOR IS 5' FROM OPENINGS. FBC-M501.3.1 |
|