2020-10-07 13:42:59 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 200900058 |
| 10/7/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7791 BLUE |
| HERON WAY SHOW A GAS PERMIT #01040720 WAS ISSUED ON |
| 4/8/2001 FOR GAS LINE INSTALLATION THAT INCLUDED A |
| FUTURE BBQ AT 40,000 BTUH. THE TOTAL DEVELOPED LENGTH |
| OF SYSTEM SHOWN IS 83 FT. TO THE COOKTOP, AND THE TOTAL |
| LOAD OF THE SYSTEM INCLUDING THE BBQ IS 378.000 BTUH. |
| PLEASE REVISE THE GAS RISER TO MATCH WITH THE APPROVED |
| PLANS ON FILE- SECTIONS G2412.3 & G2412.4 FBC RES. |
| |
| A) SHOW THE CORRECT TOTAL LOAD AND INDIVIDUAL LOADS OF |
| THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. |
| |
| B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| G2413.4.2 FBC RES. |
| |
| C) USING THE SIZING TABLE NOTED ON THE RISER- TABLE |
| 402.4(3), THE 1 IN. RISERS ARE UNDERSIZED FOR EITHER A |
| TOTAL LOAD OF 653,000 BTUH AS SHOWN ON THE DRAWING, OR |
| A POTENTIAL LOAD OF 684,000 BTUH IF USING THE LOADS |
| APPROVED UNDER PERMIT- 01040720. ACCORDING TO THE TABLE |
| A MINIMUM 1-1/4 IN. PIPE IS REQUIRED- SECTION G2413.4.1 |
| FBC RES OR 402.4.1 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |