Plan Review Notes
Plan Review Notes For Permit 20090055
Permit Number 20090055
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-19 17:17:521ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090055
 10/19/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING:
  
 A) SHOW THE BRANCH PIPING RUNS INTO THE INTERIOR OF THE
 HOUSE AND ANY EXTERIOR BRANCHES SERVING OUTDOOR
 APPLIANCES SUCH AS POOL HEATERS OR BBQ'S- SECTIONS
 G2412.3 & G2412.4 FBC RES.
  
 B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
  
 C) PROVIDE THE INDIVIDUAL APPLIANCE BTUH LOADS AND THE
 TOTAL BTUH LOAD OF THE SYSTEM- SECTIONS G2412.3,
 G2412.4, G2413.2 FBC RES.
  
 D) A 2 PSI SYSTEM IS SHOWN AT THE METER. PLEASE SHOW
 THE LOCATION OF THE EXISTING OR NEW LOW PRESSURE
 REGULATORS SERVING THE INTERIOR AND EXTERIOR
 APPLIANCES- SECTION G2421.1 & 2421.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  