2020-09-11 12:36:01 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20090025 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) CANNOT COMPLETE THE REVIEW, NOT ENOUGH INFORMATION |
| GIVEN IN THIS SUBMITTAL. FBC FS 107.2.1 |
| |
| 2) PLEASE IDENTIFY THE GENERATOR USED AND THE WEIGHT OF |
| GENERATOR ON THE GENERATOR PAD SPECS PROVIDED. FBC FS |
| 107.2.1 |
| |
| 3) PLEASE PROVIDE METHOD USED TO SIZE THIS NATURAL GAS |
| PIPING SYSTEM, I.E.; LONGEST LENGTH OR BRANCH LENGTH |
| METHOD? FBC FS 107.2.1 |
| |
| 4) PLEASE PROVIDE THE DISTANCE TO THE MOST REMOTE |
| APPLIANCE FROM THE GAS METER FOR SIZING OF THIS SYSTEM. |
| FBC FS 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |