Plan Review Notes For Permit 20090017 |
Permit Number |
20090017 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-15 11:56:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | SHOW WHERE POWER COMES FROM, LOCATION OF METER, PANEL, | | OR DISTRIBUTION AND DISTANCE TO ROOF. 215.5 | | | | NEED TO DO AN AIC RATING CALCULATION 110.9,110,10 |
|