Plan Review Notes For Permit 20090001 |
Permit Number |
20090001 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-21 15:02:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | PLAN SHOWS 2/0 WHERE IT IS NOT FEEDING THE ENTIRE LOAD. | | | | 120/240-VOLT, SINGLE-PHASE DWE LLING SERVICES AND | | FEEDERS. FOR ONE-FAMILY DWELLINGS AND THE INDIVIDUAL | | DWELLING UNITS OF TWO-FAMILY AND MULTIFAMILY DWELLINGS, | | SERVICE AND FEEDER CONDUCTORS SUPPLIED BY A | | SINGLE-PHASE, 120/240-VOLT SYSTEM SHALL BE PERMITTED BE | | SIZED IN ACCORDANCE WITH 310.15(B)(7) (1) THROUGH (4). | | | | (1) FOR A SERVICE RATED 100 THROUGH 400 A, THE SERVICE | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS | | SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL | | DWELLING UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING, | | SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 | | PERCENT OF THE SERVICE RATING | | | | |
|