Plan Review Notes
Plan Review Notes For Permit 20090001
Permit Number 20090001
Review Stop E
Sequence Number 1
Notes
Date Text
2020-10-21 15:02:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLAN SHOWS 2/0 WHERE IT IS NOT FEEDING THE ENTIRE LOAD.
  
 120/240-VOLT, SINGLE-PHASE DWE LLING SERVICES AND
 FEEDERS. FOR ONE-FAMILY DWELLINGS AND THE INDIVIDUAL
 DWELLING UNITS OF TWO-FAMILY AND MULTIFAMILY DWELLINGS,
 SERVICE AND FEEDER CONDUCTORS SUPPLIED BY A
 SINGLE-PHASE, 120/240-VOLT SYSTEM SHALL BE PERMITTED BE
 SIZED IN ACCORDANCE WITH 310.15(B)(7) (1) THROUGH (4).
  
 (1) FOR A SERVICE RATED 100 THROUGH 400 A, THE SERVICE
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING,
 SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83
 PERCENT OF THE SERVICE RATING
  
  