Plan Review Notes
Plan Review Notes For Permit 20081429
Permit Number 20081429
Review Stop M
Sequence Number 2
Notes
Date Text
2020-09-18 14:29:54PROVISO: FBC EC R4.3.3.6 AIR HANDLING UNITS
 AIR HANDLER MAY BE INSTALLED IN THE ATTIC ONLY IF THE
 FOLLOWING CONDITIONS ARE MET.
 1) THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET OF AN ATTIC ACCESS.
 2) A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT
 DOWN THE UNIT WHEN THE CONDENSATION DRAIN IS NOT
 WORKING PROPERLY.
 3) THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4) A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOME OWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR CONDITIONING SYSTEM IS EQUIPED WITH ONE OR
 BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU
 WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR
 (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  