2020-09-15 10:51:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) THE BATHROOM DOOR IS INDICATED AS OPENING INTO THE |
| PATH OF EGRESS. THE BATHROOM DOOR SHALL NOT BLOCK THE |
| EXTERIOR EXIT DOOR. |
| |
| DOES THAT EXTERIOR DOOR HAVE AN EXIT SIGN OVER IT |
| AND/OR IS IT A REQUIRED EXIT DOOR? SOME BUSINESSES CAN |
| HAVE A SINGLE EXIT (FRONT DOOR) IF IT MEETS THE CODE |
| REQUIRMENTS FOR A SINGLE EXIT. |
| |
| PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| |
| 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS SHALL |
| LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| AN AISLE, A CORRIDOR, A |
| PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT |
| PROJECT NOT MORE THAN |
| 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, |
| A PASSAGE WAY, OR A |
| LANDING, WHEN FULLY OPEN, UNLESS BOTH OF THE FOLLOWING |
| CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| PROJECTION TO |
| NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF THE |
| STAIR LANDING |
| WHEN THE DOOR LEAF IS FULLY OPEN. |
| |
| NFPA 101 CH 39 EXISTING BUSINESS |
| |
| 39.2.4.2 EXIT ACCESS, AS REQUIRED BY 39.2.4.1(3), SHALL |
| BE PERMITTED |
| TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| PERMITTED AS |
| COMMON PATHS OF TRAVEL BY 39.2.5.3. |
| |
| 39.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| AREA WITH A |
| TOTAL OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED |
| THAT ALL OF |
| THE FOLLOWING CRITERIA ARE MET: |
| (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| THE LEVEL OF |
| EXIT DISCHARGE FOR THE BUILDING. |
| (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| INCLUDING TRAVEL |
| WITHIN THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| 39.2.4.3(2) SHALL BE |
| ON THE SAME STORY, OR, IF TRAVERSING OF STAIRS IS |
| NECESSARY, SUCH |
| STAIRS SHALL NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND |
| BOTH OF |
| THE FOLLOWING ALSO SHALL APPLY: |
| (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE |
| BUILDING, WITH NO DOOR OPENINGS THEREIN. |
| (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| SHALL BE |
| PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| FT |
| (4570 MM) VERTICAL TRAVEL LIMITATION. |
| |
| IF THAT EXIT DOOR IS A REQUIRED EXIT THEN THE BATHROOM |
| DOOR SHALL NOT OPEN OUT TO BLOCK THE EXIT. THE DOOR |
| SHALL SWING INTO THE BATHROOM. |
| |
| IF THERE IS AN EXIT SIGN OVER THE DOOR BUT IS NOT A |
| REQUIRED EXIT, REMOVE THE EXIT SIGN AND THE DOOR CAN |
| REMAIN SWINGING OUT. |
| |
| THE FIRE INSPECTOR WITH VERIFY ON INSPECTION. |
| |
| PLEASE ENSURE COMPLIANCE. |
| |
| |
| |