Plan Review Notes
Plan Review Notes For Permit 20081406
Permit Number 20081406
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-09-15 10:51:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE BATHROOM DOOR IS INDICATED AS OPENING INTO THE
 PATH OF EGRESS. THE BATHROOM DOOR SHALL NOT BLOCK THE
 EXTERIOR EXIT DOOR.
  
 DOES THAT EXTERIOR DOOR HAVE AN EXIT SIGN OVER IT
 AND/OR IS IT A REQUIRED EXIT DOOR? SOME BUSINESSES CAN
 HAVE A SINGLE EXIT (FRONT DOOR) IF IT MEETS THE CODE
 REQUIRMENTS FOR A SINGLE EXIT.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL NOT
 PROJECT NOT MORE THAN
 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR,
 A PASSAGE WAY, OR A
 LANDING, WHEN FULLY OPEN, UNLESS BOTH OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO
 NOT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF THE
 STAIR LANDING
 WHEN THE DOOR LEAF IS FULLY OPEN.
  
 NFPA 101 CH 39 EXISTING BUSINESS
  
 39.2.4.2 EXIT ACCESS, AS REQUIRED BY 39.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 39.2.5.3.
  
 39.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A
 TOTAL OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED
 THAT ALL OF
 THE FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF
 EXIT DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL
 WITHIN THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 39.2.4.3(2) SHALL BE
 ON THE SAME STORY, OR, IF TRAVERSING OF STAIRS IS
 NECESSARY, SUCH
 STAIRS SHALL NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND
 BOTH OF
 THE FOLLOWING ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE
 BUILDING, WITH NO DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT
 (4570 MM) VERTICAL TRAVEL LIMITATION.
  
 IF THAT EXIT DOOR IS A REQUIRED EXIT THEN THE BATHROOM
 DOOR SHALL NOT OPEN OUT TO BLOCK THE EXIT. THE DOOR
 SHALL SWING INTO THE BATHROOM.
  
 IF THERE IS AN EXIT SIGN OVER THE DOOR BUT IS NOT A
 REQUIRED EXIT, REMOVE THE EXIT SIGN AND THE DOOR CAN
 REMAIN SWINGING OUT.
  
 THE FIRE INSPECTOR WITH VERIFY ON INSPECTION.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  