Plan Review Notes For Permit 20081406 |
Permit Number |
20081406 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-28 14:34:25 | ADD RESTROOM | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE BUILDING USE (OCCUPANCY | | CLASSIFICATION PER FBC CHAPTER 3. | | 2) PLEASE SHOW THE WALL AND FLOOR FINISHES TO COMPLY | | WITH FBC 1210.2 (DRYWALL IS NOT CONSIDERED A HARD | | SURFACE) | | 3) DOOR CANNOT SWING INTO THE PATH OF EGRESS FBC | | 1005.7.1 DOORS. | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | THAN ONE-HALF. | | 4) PLEASE SHOW THE BOTTOM OF THE MIRROR REFLECTION TO | | THE FINISHED FLOOR TO COMPLY WITH FBC ACCESSIBILITY | | 603.3 MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. | | 5) PLEASE SHOW THE BUILDING EXIT DOOR MANUVERING | | CLEARANCE TO COMPLY WITH FBC ACCESSIBILITY 404.2.4 | | |
|