Plan Review Notes For Permit 20081405 |
Permit Number |
20081405 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-25 09:10:50 | DOOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE STRUCTURAL CALCULATIONS TO DETERMINE | | THE OPENING REQUIRED WIND DESIGN PRESSURES OR PROVIDE | | SIGNED AND SEALED WIND DESIGN PRESSURES FOR THE | | OPENINGS FROM AN ARCHITECT OR ENGINEER FBC 1609.1.1 | | (RISK CATEGORY IV BUILDING - 180MPH WIND SPEEDS) | | 2) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA | | STATE PRODUCT APPROVAL FOR THE "SIDE LIGHT" (FRONT | | DOOR)(FRONT PAGES AND THE INSTALLATION INSTRUCTIONS). | | | | FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG | | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON | | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW | | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] | | AND ASKING FOR THE FORM. |
|