Plan Review Notes
Plan Review Notes For Permit 20081405
Permit Number 20081405
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-25 09:10:50DOOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE STRUCTURAL CALCULATIONS TO DETERMINE
 THE OPENING REQUIRED WIND DESIGN PRESSURES OR PROVIDE
 SIGNED AND SEALED WIND DESIGN PRESSURES FOR THE
 OPENINGS FROM AN ARCHITECT OR ENGINEER FBC 1609.1.1
 (RISK CATEGORY IV BUILDING - 180MPH WIND SPEEDS)
 2) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE "SIDE LIGHT" (FRONT
 DOOR)(FRONT PAGES AND THE INSTALLATION INSTRUCTIONS).
  
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.