Plan Review Notes For Permit 20081386 |
Permit Number |
20081386 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-31 11:54:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS OF THE LOCATIONS OF THE | | PROPOSED TENTS. | | | | PLEASE PROVIDE EACH TENT LOCATION. | | | | | | | | | | 1A) PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT THESE | | TENTS WILL BE USED FOR AND WHAT TYPE OF EVENTS ARE | | PROPOSED? | | | | PLEASE PROVIDE DETAL FOR EACH TENT AND WITHIN THE GATED | | AREA. | | | | | | | | 1B) THERE ARE NO FLOOR PLANS SHOWING INTERIOR LAYOUTS | | TO ENSURE OPEN WALKWAYS THAT LEAD TO EXITS. | | | | PLEASE PROVIDE DETAILED FLOOR PALNS INCLUDING ALL | | EXITS. | | | | | | | | 2) THERE ARE NO IDICATIONS OF TIE DOWNS/ANCHORING. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 4) THERE APPEARS TO BE A FENCE INDICATED. PLEASE | | CONFIRM. | | | | THERE ARE NO INDICATIONS OF THE SIZE OF THE FENCE GATES | | OR HOW THEY CAN BE OPENED TO EXIT. | | | | PLEAE PROVIDE FENCE GATE DETAILS. | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|