2020-08-31 10:43:21 | PLAN REVIEW - BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| |
| TEMPORARY MEMBRANE STRUCTURES |
| (TENTS) |
| CHPT. 1 FBC |
| |
| SECTION 108 |
| TEMPORARY STRUCTURES AND USES |
| |
| 1. CONFORMANCE PER SECTION 3103.1.1 |
| TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| HEALTH, SAFETY AND GENERAL WELFARE. |
| A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| STRUCTURES WITH SPANS OF 40 FEET OR GREATER. |
| |
| 2. FOUNDATION/TIE DOWN |
| A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT |
| B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL |
| MOVEMENT |
| |
| |
| **ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 40 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| NO EXCEPTIONS BY ORDER OF THE BUILDING OFFICIAL |
| |
| |
| |
| |