2020-09-17 22:43:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL SUB-PERMIT APPLICATION SAYS "FIXTURE |
| REPLACEMENTS". THERE IS MORE WORK THAN "FIXTURE |
| REPLACMENT ONLY" SHOWN ON PLAN. PROVIDE PERMIT |
| APPLICATION WITH ACCURATE DESCRIPTION. FBC 107.2.1 |
| |
| 2. PROVIDE PLAN THAT CLEARLY ANNOTATES WORK TO BE |
| COMPLETED. IS THIS A FULL GUT REMODEL OF APARTMENT? IF |
| SO, THE PLAN PROVIDED IS NOT TO CURRENT 2014 NEC. |
| PROVIDE CORRECTIONS. |
| |
| 3. PROVIDE NOTE ON PLAN THAT LOW VOLTAGE SHOWN WILL |
| REQUIRE SEPARATE PERMIT. FBC 107.2.1 105.1 |
| |
| 4. SMOKE DETECTORS ARE TO BE HARD WIRED PER FBC-R 314& |
| 315. NOTES ON PLAN ARE CONFLICTING AND STATE THAT |
| "SMOKE ALARMS ARE EXISTING 10 YEAR BATTERY" THEN |
| ANOTHER NOTES STATES "SMOKE ALARMS WILL BE HARD WIRED". |
| |
| 5. WITH INFORMATION AND PLAN PROVIDED A COMPLETE REVIEW |
| COULD NOT BE MADE. SUBMIT PLAN WITH CLEAR SCOPE OF |
| WORK. ADDITIONAL PLAN REVIEW COMMENT MAY OCCUR AFTER |
| RESUBMISSION. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |