Plan Review Notes
Plan Review Notes For Permit 20081382
Permit Number 20081382
Review Stop E
Sequence Number 1
Notes
Date Text
2020-09-17 22:43:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL SUB-PERMIT APPLICATION SAYS "FIXTURE
 REPLACEMENTS". THERE IS MORE WORK THAN "FIXTURE
 REPLACMENT ONLY" SHOWN ON PLAN. PROVIDE PERMIT
 APPLICATION WITH ACCURATE DESCRIPTION. FBC 107.2.1
  
 2. PROVIDE PLAN THAT CLEARLY ANNOTATES WORK TO BE
 COMPLETED. IS THIS A FULL GUT REMODEL OF APARTMENT? IF
 SO, THE PLAN PROVIDED IS NOT TO CURRENT 2014 NEC.
 PROVIDE CORRECTIONS.
  
 3. PROVIDE NOTE ON PLAN THAT LOW VOLTAGE SHOWN WILL
 REQUIRE SEPARATE PERMIT. FBC 107.2.1 105.1
  
 4. SMOKE DETECTORS ARE TO BE HARD WIRED PER FBC-R 314&
 315. NOTES ON PLAN ARE CONFLICTING AND STATE THAT
 "SMOKE ALARMS ARE EXISTING 10 YEAR BATTERY" THEN
 ANOTHER NOTES STATES "SMOKE ALARMS WILL BE HARD WIRED".
  
 5. WITH INFORMATION AND PLAN PROVIDED A COMPLETE REVIEW
 COULD NOT BE MADE. SUBMIT PLAN WITH CLEAR SCOPE OF
 WORK. ADDITIONAL PLAN REVIEW COMMENT MAY OCCUR AFTER
 RESUBMISSION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  