2020-10-27 15:19:14 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT-20081365 |
| |
| CODES IN EFFECT: |
| |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE LONGEST LENGTH OF PIPING FROM THE |
| POINT OF DELIVERY TO THE MOST REMOTE OUTLET. THIS COULD |
| EITHER BE THE EXISTING SYSTEM OR THE NEW PIPING BEING |
| INSTALLED BUT I MUST HAVE THIS NUMBER AS IT IS THE |
| NUMBER USED WHEN SIZING THE NEW GAS PIPING. FBC GF |
| 402.4.1 |
| |
| 2) PLEASE SEE NOTE 2 OF MY ORIGINAL REVIEW: PLEASE |
| PROVIDE THE GENERATOR PAD SPECS. FBC 107.2 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |