Plan Review Notes
Plan Review Notes For Permit 20081355
Permit Number 20081355
Review Stop M
Sequence Number 3
Notes
Date Text
2020-11-06 10:50:592ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20081355
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS STATED IN THE FIRST REVIEW COMMENTS; WE HAVE NO
 RECORDS OF A PERMITTED MECHANICAL SYSTEM EVER BEING
 INSTALLED AT THIS ADDRESS. WE MUST CONSIDER THIS AS A
 NEW INSTALLATION AND NOT A CHANGE OUT. PLEASE ADJUST
 THE PERMIT APPLICATION TO A NEW MECHANICAL SYSTEM
 INCLUDING DUCT WORK. FBC 107.1
  
 2) PLEASE ADJUST THE VALUE GIVEN ON THE PERMIT
 APPLICATION TO REFLECT THE COST OF A NEW MECHANICAL
 SYSTEM. FBC 107.1
  
 3) PLEASE REMOVE ALL A/C CHANGE OUT DOCUMENTS AS THIS
 IS NOT CONSIDERED A CHANGE OF USE. FBC 107.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  