2020-10-06 12:26:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081355
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WE HAVE NO RECORDS OF A PERMITTED MECHANICAL SYSTEM
 FOR THIS ADDRESS. WE MUST CONSIDER THIS AS A NEW SYSTEM
 AND NOT A CHANGE OUT. PLEASE PROVIDE THE ENERGY
 CALCULATIONS AND THE MANUAL J FOR THIS PROJECT. FBC E
 101.5.1.1.2 AND FBC EC R 403.7
  
 2) IT APPEARS THAT THE ENTIRE DUCTWORK IS NEW. PLEASE
 UPDATE THE PERMIT APPLICATION TO REFLECT A NEW
 MECHANICAL SYSTEM FOR THIS ADDRESS. FBC 107.2.1
  
 3) IT APPEARS THE VALUE FOR THIS NEW SYSTEM IS LOW.
 PLEASE ADJUST THE VALUE ON THE APPLICATION. FBC 109.3
  
 4) PLEASE PROVIDE DUCT SIZES ON THE DRAWING FOR THE
 RETURN DUCTS. PLEAS MAKE SURE THEY MEET: FBC RES
 M1602.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  