2020-10-06 12:26:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20081355 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) WE HAVE NO RECORDS OF A PERMITTED MECHANICAL SYSTEM |
| FOR THIS ADDRESS. WE MUST CONSIDER THIS AS A NEW SYSTEM |
| AND NOT A CHANGE OUT. PLEASE PROVIDE THE ENERGY |
| CALCULATIONS AND THE MANUAL J FOR THIS PROJECT. FBC E |
| 101.5.1.1.2 AND FBC EC R 403.7 |
| |
| 2) IT APPEARS THAT THE ENTIRE DUCTWORK IS NEW. PLEASE |
| UPDATE THE PERMIT APPLICATION TO REFLECT A NEW |
| MECHANICAL SYSTEM FOR THIS ADDRESS. FBC 107.2.1 |
| |
| 3) IT APPEARS THE VALUE FOR THIS NEW SYSTEM IS LOW. |
| PLEASE ADJUST THE VALUE ON THE APPLICATION. FBC 109.3 |
| |
| 4) PLEASE PROVIDE DUCT SIZES ON THE DRAWING FOR THE |
| RETURN DUCTS. PLEAS MAKE SURE THEY MEET: FBC RES |
| M1602.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |